beautypg.com

Red Lion GEMINI 33 User Manual

Page 32

background image

INSTALLATION & REMOVAL OF THE RELAY BOARD

To install the relay board, locate the relay opening at the lower right-hand

corner, on the back of the Gemini 3300. Pull the tab down while sliding the

board into the two slots in the housing. The relay board will seat into the unit,

allowing the tab to return to its original position. To remove the relay board,

pull down on the tab just enough to allow the relay board to slide out. Grasp

the terminal block and pull to remove the board.

NOTES:

1. SENSOR VOLTAGE AND CURRENT

The +12 V sensor supply voltage on the “DC OUT” terminal is nominal

with +/-25% variation due to line and internal load variations. All RLC

sensors will accommodate this variation.

2. HI/LO FRQ SELECTION

The HI/LO FRQ selection switch must be set on “LO FRQ” when switch

contacts are used to generate count input signals. Since the “LO FRQ”

mode also provides very high immunity against electrical noise pickup, it

is recommended that this mode also be used, whenever possible, with

electronic sensor outputs. The “LO FRQ” mode can be used with any type

of sensor output, provided count pulse widths never decrease below 5

msec, and the count rate does not exceed 100 cps.

3. V

IL

and V

IH

levels given are nominal values +/-10% when counter voltage

on “DC OUT” terminal is +12 VDC. These nominal values will vary in

proportion to the variations in the “DC OUT” terminal voltage, which are

caused by line voltage and load changes.

4. When shielded cable is used, the shield should be connected to “COMM.”

at the counter and left unconnected at the sensor end.

5. Input B setup is identical to that of Input A. Input B is for logic inputs only.

6. Inputs A and B can accept source pulses from other circuits up to +28 V in

amplitude. For voltages above +28 V, a limiting resistor and zener diode

should be used to limit the voltage at the input.

-30-