7.2.2
Table of possible error messages in the bus module
The following error messages concern bus-related messages, which are indicated on the EtherCAT module
SK TU4-ECT(-…))
Error number
Group
Details in
P170
Fault
Text in the ParameterBox
Cause
Remedy
1000 EEPROM
error
Module faulty
1010
System bus 24V missing
Check connections and supply cables
Ensure 24V voltage supply
1020
System bus timeout
Check time set in parameter (P151).
Telegram transfer is faulty.
Check external connection
Check bus protocol program process.
Check bus master.
1030
System bus OFF
Check connections and supply cables
Ensure 24V voltage supply
Check bus master.
5400 EtherCAT
ASIC
Error
No contact with ASIC
ASIC faulty or
EEPROM faulty
5401
EtherCAT buffer overflow
Message box (message buffer) for the module was
overwritten by a new telegram before processing
E1000
5420 EtherCAT
timeout
Telegram transfer is faulty.
Check external connection.
Check bus protocol program process.
Check bus master.