beautypg.com

NORD Drivesystems BU0270 User Manual

Page 65

background image

7 Error monitoring and error messages

BU 0270 GB

Subject to technical amendments

65

7.2.2

Table of possible error messages in the bus module

The following error messages concern bus-related messages, which are indicated on the EtherCAT module
SK TU4-ECT(-…))

Error number

Group

Details in
P170

Fault

Text in the ParameterBox

Cause

Remedy

1000 EEPROM

error

Module faulty

1010

System bus 24V missing

Check connections and supply cables

Ensure 24V voltage supply

1020

System bus timeout

Check time set in parameter (P151).

Telegram transfer is faulty.

Check external connection

Check bus protocol program process.

Check bus master.

1030

System bus OFF

Check connections and supply cables

Ensure 24V voltage supply

Check bus master.

5400 EtherCAT

ASIC

Error

No contact with ASIC

ASIC faulty or

EEPROM faulty

5401

EtherCAT buffer overflow

Message box (message buffer) for the module was
overwritten by a new telegram before processing

E1000

5420 EtherCAT

timeout

Telegram transfer is faulty.

Check external connection.

Check bus protocol program process.

Check bus master.