NORD Drivesystems BU0270 User Manual

Page 52

background image

Supplementary Manual EtherCAT for NORDAC SK 200E

52

Subject to technical amendments

BU 0270 GB

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P543

[-01]

...

[-03]

Actual bus value 1 3

S

P

The return value can be selected for bus actuation in this parameter.

NOTE:

For further details, please refer to the description of (P418).

… [-01] =

Actual bus value 1

… [-02] =

Actual bus value 2

… [-03] =

Actual bus value 3

Possible values which can be set:

0 ... 22

{ [-01] = 01 }

{ [-02] = 04 }

{ [-03] = 09 }

0 =

Off

1 =

Actual frequency

2 =

Actual speed

3 =

Current

4 =

Torque current (100% = P112)

5 =

State of digital inputs and outputs

2

6 =

... 7 Reserved

8 =

Setpoint frequency

9 =

Error number

10 =

... 11 Reserved

12 =

Bus Out bits 0...7

13 =

... 16 Reserved

17 =

Value analog input 1 (P400)

18 =

Value analog input 2 (P405)

19 =

Setpoint frequency master value (P503)

20 =

Setpoint frequency after master value ramp

21 =

Actual frequency without master value slip

22 =

Speed from encoder

P546

[-01]

...

[-03]

Function Bus setpoint 1 ... 3

S

P

In this parameter, a function is allocated to the output setpoint during bus actuation.

NOTE:

For further details please refer to the description of (P400).

… [-01] =

Actual bus value 1

… [-02] =

Actual bus value 2

… [-03] =

Actual bus value 3

Possible values which can be set:

0 ... 24

{ [-01] = 01 }

{ [-02] = 00 }

{ [-03] = 00 }

0 =

Off

1 =

Setpoint frequency (16 bit)

2 =

Frequency addition

3 =

Frequency subtraction

4 =

Minimum frequency

5 =

Maximum frequency

6 =

PI process controller actual value

7 =

PI process controller setpoint

8 =

Actual frequency PID

9 =

Actual PID frequency limited

10 =

Actual PID frequency monitored

11 =

Limiting torque current

12 =

Torque current switch-off limit

13 =

Limiting current

14 =

Current switch-off limit

15 =

Ramp time

16 =

Lead torque (P214) multiplication

17 =

Servo mode torque

18 =

Curve travel calculator

19 =

Digital In bits 0...7

20 =

...24 reserved for Posicon

2

The assignment of the digital inputs for P543 = 5

Bit 0 = DigIn 1

Bit 1 = DigIn 2

Bit 2 = DigIn 3

Bit 3 = DigIn 4

Bit 4 = Reserved

Bit 5 = Reserved

Bit 6 = Reserved

Bit 7 = Reserved

Bit 8 = Reserved

Bit 9 = Reserved

Bit 10 = Reserved

Bit 11 = Reserved

Bit 12 = Out 1

Bit 13 = Out 2

Bit 14 = Reserved

Bit 15 = Reserved