2 error messages 7.2.1 – NORD Drivesystems BU0270 User Manual

Page 64

background image

Supplementary Manual EtherCAT for NORDAC SK 200E

64

Subject to technical amendments

BU 0270 GB

7.2 Error messages

7.2.1

Table of possible error messages (caused by the bus) in the frequency inverter

The following error messages concern bus-related messages which are indicated on the frequency inverter. A
complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).

Error code

display on the
SimpleBox

Group

Details in
P700 / P701

Fault

Text in the ParameterBox

Cause

Remedy

10.0 Connection

error

Contact to SK TU4-ECT interrupted. (SK 500E)

10.1 ASIC

errors

No communication with the EtherCAT- ASIC.

~ ASIC fault,
~ EEPROM not initialised or faulty)

This error can only be reset by switching off the 24V supply
voltage.

10.2 Timeout

EtherCAT

watchdog

Telegram transfer is faulty.

Check external connection.

Check bus protocol program process.

Check bus master.

10.3 Timeout

via

(P151)

Telegram transfer is faulty.

Check watchdog time (P151)

Check physical bus connections

Contains cyclic telegrams

10.5 General

EtherCAT

configuration error

A general configuration error has occurred.

10.8

Timeout - connection error

The connection between the FI and the SK TU4-ECT had a
timeout

E010

10.9

Module missing / P120

The module entered in parameter (P120) is not available.