2 error messages 7.2.1 – NORD Drivesystems BU0270 User Manual
Page 64
Supplementary Manual EtherCAT for NORDAC SK 200E
64
Subject to technical amendments
BU 0270 GB
7.2 Error messages
7.2.1
Table of possible error messages (caused by the bus) in the frequency inverter
The following error messages concern bus-related messages which are indicated on the frequency inverter. A
complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).
Error code
display on the
SimpleBox
Group
Details in
P700 / P701
Fault
Text in the ParameterBox
Cause
Remedy
10.0 Connection
error
Contact to SK TU4-ECT interrupted. (SK 500E)
10.1 ASIC
errors
No communication with the EtherCAT- ASIC.
~ ASIC fault,
~ EEPROM not initialised or faulty)
This error can only be reset by switching off the 24V supply
voltage.
10.2 Timeout
EtherCAT
watchdog
Telegram transfer is faulty.
Check external connection.
Check bus protocol program process.
Check bus master.
10.3 Timeout
via
(P151)
Telegram transfer is faulty.
Check watchdog time (P151)
Check physical bus connections
Contains cyclic telegrams
10.5 General
EtherCAT
configuration error
A general configuration error has occurred.
10.8
Timeout - connection error
The connection between the FI and the SK TU4-ECT had a
timeout
E010
10.9
Module missing / P120
The module entered in parameter (P120) is not available.