5 EtherCAT - Data transfer

BU 0270 GB

Subject to technical amendments

41

It is also possible to only transmit the Low component of the position. This results in a limited value range
(16Bit) from +32,

767

rotations to -32,

768

rotations. This value range can be extended with the aid of the gear

ratio factor (P607 & P608). However, it must be noted that there is an according reduction in the resolution.

5.2.2

The status machine

The frequency inverter passes through a status machine. The changes between various states are triggered
by the respective control commands in the process data control word. The actual status is returned in the
process data status word.
After switching on, the frequency inverter is in “Switch-on disabled” status. This status can only be ended by
transmitting the “Shut down (Off 1)” command.
The answer to a master telegram normally does not yet contain a reaction to the control command. The
controller must check the answers from the slaves as to whether the control command has been carried out.
The following bits indicate the status of the frequency inverter:

Status

Bit 6

Switch-on

disable

Bit 5

Emergency

stop

Bit 4

Disable

voltage

Bit 3

Fault

Bit 2

Operation

enabled

Bit 1

Standby

Bit 0

Ready for

switch-on

Not ready to start

0

X

X

0

0

0

0

Starting

disabled 1 X X 0 0 0 0

Ready

to

start

0 1 1 0 0 0 1

Activated

0 1 1 0 0 1 1

Operation

enabled 0 1 1 0 1 1 1

Fault

0 X X 1 0 0 0

Error

active

0 X X 1 1 1 1

Emergency

stop

active

0 0 1 0 1 1 1

Codes for FI status