2 process data (pdo communication) – NORD Drivesystems BU0270 User Manual

Page 35

background image

5 EtherCAT - Data transfer

BU 0270 GB

Subject to technical amendments

35

5.2 Process data (PDO communication)

The process data is transmitted via PDOs These are fixed and cannot be changed.
Control words and setpoints are transferred from the bus master to the SK TU4-ECT as process data and in
return, the status word and actual values from the SK TU4-ECT are sent to the bus master from the FI. This
transfer is carried out cyclically and the master can access these process values directly, as they are stored in
the I/O area.
Via the SK TU4-ECT, up to 4 FIs and the SK TU4-ECT itself can be accessed, whereby in the basic setting,
only one SK 200E frequency inverter is integrated. This prevents unnecessary data from being transported in
the telegram, which would increase the bus load.

The process data structure for an individual FI contains 8 Bytes of inverter data.

Direction of transmission

Transmitted data (8 Byte)

1st word

2nd word

3rd word

4th word

Transmission to SK TU4-ECT

Control word

Setpoint 1

Setpoint 2

Setpoint 3

Reception from the SK TU4-ECT Status word

Actual value 1 Actual value 2 Actual value 3


The process data structure for the bus module includes 2 Bytes, of which only the Low Byte is used.

Transmitted data (2 Byte)

Direction of transmission

Low byte

High byte

Bit 0

Bit 1

Bit 2

Bit 3

Bit 4

Bit 5

Bit 6

Bit 7

Bit 8 … Bit 15

Transmission to SK TU4-ECT

DOut1

DOut2 -

-

-

-

-

-

Not used

Reception from the SK TU4-ECT DIN1

DIN2

DIN3

DIN4

DIN5

DIN6

DIN7

DIN8

Not used



In the minimal configuration 8 Bytes of process data are sent in a single telegram (control of exactly one
frequency inverter). In the maximum configuration there are 34 Bytes (I/Os of the bus module (2 Bytes) + 4
frequency inverters (4 x 8 Bytes)).

The assignment of values in the setpoint/actual value area is carried out:
in the SK 200E via the parameters P543 [-01 … -03] and P546 [-01 … -03],
in the SK 500E via the parameters P543 to P548.

Structure of the process data telegram from the SK TU4-ECT for an FI