NORD Drivesystems BU0270 User Manual
Page 60
Supplementary Manual EtherCAT for NORDAC SK 200E
60
Subject to technical amendments
BU 0270 GB
6.2.3
Module information parameters specific to the bus (P180)
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P180 NMT
State
Display of communication level
0 ... 8
dec
1 = Init
2 = Pre-Operational
4 = Save-Operational
8 = Operational
P181 Second
Address
0 ... 2047
Display of the "Second Address" set via the DIP switches
P182 EtherCAT
Watchdog
0 ... 65535 ms
1 … 65535 = Watchdog monitoring time
0 = Watchdog inactive
P183
…
[-01]
…
…
[-04]
EtherCAT transfer error
0 ... 0xFF
Display of error which has occurred on the EtherCAT level
… [-01] =
0x300 error on the RX port
… [-02] =
0x302 error on the TX port
… [-03] =
0x310 lost link on the RX port
… [-04] =
0x311 lost link on the TX port
P184
SPI ASIC error
0 ... 0xFFFF
Counts transmission errors between the ASIC and the SK TU4-ECT processor. As default, this
value is set to 1. This error can be caused by the effect of EMC.