Supplementary Manual EtherCAT for NORDAC SK 200E

32

Subject to technical amendments

BU 0270 GB

• The missing modules can be added in the TwinCAT System Manager. For this, the SK TU4-ECT box

is highlighted and the index "Slots" is selected (see illustration below).

• Here, the required configuration can be produced. After the settings are complete, the new

configuration must be loaded into the SK TU4-ECT. This can be carried out via the function "Activate
configuration" or by "Reboot TwinCAT in configuration mode".

• With this, the SK TU4-ECT is now integrated

Bus address via DIP switches (Second Address)
If the integrated bus module is to be assigned with a fixed address (DIP switches, see Section 2.2.3), then this
setting must be updated in the TwinCAT System Manager as follows:

• Highlight the SK TU4-ECT and select "Add to Hot Connection Groups" using the right-hand mouse

button.

• In the dialogue which opens, select "2. Address" and enter the DIP address ( see also (P181)).
• Finish

ATTENTION

Devices without "Second Address" functionality must always be physically located at the
start of the bus. A device without this functionality may not follow a device with "Second
Address" functionality in the EtherCAT bus line.

TwinCAT System Manager, editing the slots