Supplementary Manual EtherCAT for NORDAC SK 200E

46

Subject to technical amendments

BU 0270 GB

Relevant

bus system

Serial

No.

Step

Comments

Field bus

(EtherCAT)

6

Configure bus
module for field
bus

EtherCAT address assignment is carried out automatically.
Exception: Second Address Mode (see Section 2.2.3).

System bus

7

Monitoring at
system bus level

• (P151):

{ 200 }

• (P120 [-01])

{ 1 } or { 2 }

System bus

8

Checking system
bus
communication

• (P748):

"System bus status"

• (P740 [-01]):

"Control word"

• (P740 [-02]):

"Setpoint 1"

• (P741 [-01]):

"Status word"

• (P741 [-02]):

"Actual value 1"

• (P173):

"Module status"

Field bus

(EtherCAT)

9

Checking field bus
communication

• (P173):

"Module status"

• (P176):

"PZD Bus In"

• (P177):

"PZD Bus Out"

Note:

Settings specific to the application (motor data, control parameters, control terminal functions etc.)

cannot of course be described here.

5.4.2

Example for switching the frequency inverter on and off

In this example, a FI will be operated with a setpoint (setpoint frequency) and an actual value (actual
frequency). The "Maximum Frequency" is 50Hz.

Parameter settings:

• P105 = 50
• P543 = 1
• P546 = 1

Control
word

Setpoint 1

Status

word

Actual

value 1

Explanation

- - -

- - -

0000

hex

0000

hex

- - -

- - -

xx40

hex

0000

hex

The mains voltage is switched on at the FI

047E

hex

0000

hex

xx31

hex

0000

hex

FI is set to "Standby" status

047F

hex

2000

hex

xx37

hex

2000

hex

FI is set to "Operation enabled" status and controlled with a
50% setpoint.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 25Hz.

047E

hex

2000

hex

xx31

hex

0000

hex

FI is set to "Standby" status, the motor runs up its
parameterised ramp to speed 0 and is switched off.

The FI is disabled again and the motor is without current.

047F

hex

1000

hex

xx37

hex

1000

hex

FI is set to "Operation enabled" status and controlled with a
25% setpoint.

The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5Hz.


5.5 Timeout monitoring

Data traffic on the EtherCAT side is monitored by EtherCAT watchdogs. In addition,monitoring via the
parameter P151 of the bus module and via the relevant parameter settings in the frequency inverter is also
possible. Further details are described in Section 7.