NORD Drivesystems BU0270 User Manual
Page 50
Supplementary Manual EtherCAT for NORDAC SK 200E
50
Subject to technical amendments
BU 0270 GB
6.1.3
Supplementary parameters (P500)
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P509
Control word source
S
0 ... 4
{ 0 }
Selection of the interface via which the FI is controlled.
0 = Control terminals or keyboard control**
with the SimpleBox (if (P510)=0), the
ParameterBox or via BUS I/O Bits.
1 = Only control terminals *
, the FI can only be controlled via the digital and analog input
signals or via the bus I/O bits.
2 = USS *
, the control signals (enable, rotation direction, etc.) are transferred via the RS485
interface, the setpoint via the analog input or the fixed frequencies.
3 = System bus
*
4 = System bus broadcast *
*) Keyboard control (SimpleBox, ParameterBox, PotentiometerBox) is disabled,
parameterisation is still possible.
**) If the communication during keyboard control is interrupted (time out 0.5 sec), the
FI will disable without an error message.
NOTE:
For details of the optional bus systems, please refer to Manual BU 0250.
- www.nord.com –
As an alternative to setting the parameter, System Bus Broadcast can be selected with DIP
switch 3.
P510
... [-01]
... [-02]
Setpoint source
S
Selection of the setpoint source to be parameterised.
… [-01] =
Main setpoint source
… [-02] =
Subsidiary setpoint source
Selection of the interface via which the FI receives the setpoint.
0 ... 4
{ [-01] = 0 }
{ [-02] = 0 }
5 = Auto:
the source of the auxiliary setpoint is
automatically derived from the setting in the
parameter P509 >Interface<
6 = Control terminals
, digital and analog inputs
control the frequency, including fixed frequencies
7 = USS
8 = System bus
9 = System bus broadcast
P513 Telegram
downtime
S
-0.1 / 0.0 /
0.1 ... 100.0 s
{ 0.0 }
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next
one must arrive within the set period. Otherwise the FI reports an error and switches off with the
error message E010 >Bus Time Out<.
0.0 = Off
: Monitoring is switched off.
-0.1 = No error
: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Box removed, etc.), the FI will continue to operate unchanged.
Note:
In BUS mode (e.g.: EtherCAT), monitoring is controlled via parameter (P120). Settings in
parameter (P513) are therefore not necessary.
Caution: If a setting is made in this parameter in spite of this, values lower than 0.6s cause an
error in the FI due to the fixed definition of the system bus baud rate.