6 Parameterisation

BU 0270 GB

Subject to technical amendments

51

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P514

CAN baud rate (system bus)

S

Setting of the transfer rate (transfer speed) via the system bus interface. All bus participants
must have the same baud rate setting.

0 =

10kBaud

1 =

20kBaud

2 =

50kBaud

3 =

100kBaud

4 =

125kBaud

5 =

250kBaud**

6 =

500kBaud

7 =

1Mbaud *

0 ... 7

{ 5 }**

*) Safe operation cannot be guaranteed

**) for communication with the bus module, the parameter must be left at the factory setting
(250kBaud) otherwise no communication is possible.

P515

...

[-01]

...

[-03]

CAN address (system bus)

S

Setting of the system bus address.

0 ... 255 dec

{ all 32 dec}

or { all 20 hex}

… [-01] =

Receive address for system bus

… [-02] =

Broadcast – Receive address for system bus (slave)

… [-03] =

Broadcast – Transmit address for system bus (master)

NOTE:

If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows

FI 1 = 32, FI 2 = 34, FI 3 = 36, FI 4 = 38.

The system bus addresses should be set via the DIP switches 1/2 (Section 2.2.3).