Supplementary Manual EtherCAT for NORDAC SK 200E

40

Subject to technical amendments

BU 0270 GB

5.2.1.3 Setpoints and actual values (process values)

The meaning of the setpoint and actual values in the relevant frequency inverter is defined as follows:

Direction of transmission

Process value

SK 200E

SK 500E

Setpoint 1

P546 [-01]

P546

Setpoint 2

P546 [-02]

P547

Order to FI

Setpoint 3

P546 [-03]

P548

Actual value 1

P543 [-01]

P543

Actual value 2

P543 [-02]

P544

Status message from FI

Actual value 3

P543 [-03]

P545

Word:

PZD1

PZD2 PZD3 PZD4

Order STW SW1

SW2

SW3

Response ZSW

IW1

IW2

IW3

Bits

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0



The transfer of setpoint and actual values is carried out by three different methods, which will be explained below.

Percentage transfer
The process value is transferred as a whole number with a value range of -32768 to 32767 (8000 hex to 7FFF
hex). The value 16384 (4000 hex) is equal to 100%. The value -16384 (C000 hex) is equal to -100%.
For frequencies(setpoint frequency, actual frequency, frequency addition, actual frequency PID, …), the 100%
value corresponds to the FI parameter "Maximum Frequency" (P105) and for currents, this is the FI parameter
"Torque Current Limit" (P112) Frequencies and currents result from the following formulae.

16384

105

P

value

Frequency

×

=

16384

112

P

value

Current

×

=

Value = the 16Bit actual or setpoint value transmitted via EtherCAT

Binary transmission
Inputs and outputs as well as Digital In bits and Bus Out bits are evaluated for each bit.

Transmission of positions
For positions, a value range from +/- 50000.000 rotations is available. A motor rotation can be divided into a
maximum of 1000 steps. This scaling is independent of the encoder which is used.
The 32Bit value range is divided into a Low and a High word, so that 2 setpoint/actual values are required for
transmission. For this, it does not matter which of the 3 process data words is used.

Direction of transmission

Transmitted data (8 Byte)

1st word

2nd word

3rd word

4th word

Transmission to SK TU4-ECT

Control word

32Bit setpoint

Setpoint 3

Reception from the SK TU4-ECT Status word

Actual value 1 32Bit actual value

Depiction of 32Bit setpoint/actual values

Formula: Formation of 16Bit setpoint/actual value