L {N} {P} {DATA} N *
where {DATA} is indeterminate. If the immediately-preceding message received
by the slave Controller was not a Type 3 message, the Type 4 message is ignored.
O075-5
5-5
PM-0075
{DATA} Content
Sign/Decimal Point Position
{DATA} Content
Sign/Decimal Point Position
abcd0
+abcd
abcd5
−
abcd
abcd1
+abc.d
abcd6
−
abc.d
abcd2
+ab.cd
abcd7
−
ab.cd
Table 5-1 {DATA} Element - Sign and decimal Point Position
Identifier
Parameter/Command
Identifier
Parameter/Command
A
Setpoint High Limit
W
Output Power (Read Only if not in
Manual Control)
B
Output 1 Power Limit
Z
Controller Commands
3
C
Alarm 1 value
[
Recorder Output Scale Max.
D
Rate (Derivative Time Constant)
1
\
Recorder Output Scale Min.
E
Alarm 2 value
]
Scan Table
F
ON/OFF Differential
^
Setpoint Ramp Rate
G
Scale Range Max. (Read Only)
a
Alarm 1 Hysteresis value
H
Scale Range Min. (Read Only)
b
Alarm 2 Hysteresis value
I
Reset (Integral Time Constant)
1
c
Heater Current High Scale Limit
J
Manual Reset (Bias)
d
Heater Current Nominal Value
K
Overlap/Deadband
e
Heater Current (Read Only)
L
Controller Status
2
f
High Heater Break Alarm value
M
Process Variable
g
Low Heater Break Alarm value
N
Output 1 Cycle Time
h
AM Key Usage (Read Only)
O
Output 2 Cycle Time
i
Control Setpoint value (Read Only)
P
Proportional Band 1
1
j
Soft Start Setpoint value
Q
Scale Range Decimal Point Position
(Read Only)
k
Soft Start Time value
S
Setpoint value
l
Soft Start Time Remaining (Read
Only)
T
Setpoint Low Limit
m
Input Filter Time Constant
U
Proportional Band 2
1
v
Process Variable Offset value
V
Deviation value
Table 5-2 Commands/Parameters and Identifiers