Product specification, Universal input, General – West Control Solutions N6600 User Manual
Page 100: Thermocouple, Aproduct specification
A
PRODUCT SPECIFICATION
A.1
UNIVERSAL INPUT
General
Maximum per Controller:
One
Input Sample Rate:
Four samples/second
Digital Input Filter:
Time constant selectable from front panel -
0.0 (i.e. OFF), 0.5 to 100.0 seconds in
0.5-second increments.
Input Resolution:
14 bits approximately; always at least four
times better than display resolution.
Input Impedance:
Greater than 100M
Ω
resistive.
Isolation:
Universal input isolated from all outputs
except SSR at 240V AC.
Process Variable Offset:
Adjustable
±
input span.
Thermocouple: Ranges selectable from front panel:
A-1
S075-A
PM-0075
Type
Input Range
Dislayed Code
Type
Input Range
Displayed Code
R
0 - 1650
°
C
1127
J
32 - 1401
°
F H
1420
R
32 - 3002
°
F
1128
T
-200 - 262
°
C
1525
S
0 - 1649
°
C
1227
T
-328 - 503
°
F
1526
S
32 - 3000
°
F
1228
T
0.0 - 260.6
°
C
1541
J
0.0 - 205.4
°
C
1415
T
32.0 - 501.0
°
F
1542
J
32.0 - 401.7
°
F
1416
K
-200 - 760
°
C
6726
J
0 - 450
°
C
1417
K
-328 - 1399
°
F
6727
J
32 - 842
°
F
1418
K
-200 - 1373
°
C
6709
J
0 - 761
°
C *
1419
K
-328 - 2503
°
F
6710
* Default (not North America)
Continued overleaf.......
H