beautypg.com

Product specification, Universal input, General – West Control Solutions N6600 User Manual

Page 100: Thermocouple, Aproduct specification

background image

A

PRODUCT SPECIFICATION

A.1

UNIVERSAL INPUT

General

Maximum per Controller:

One

Input Sample Rate:

Four samples/second

Digital Input Filter:

Time constant selectable from front panel -

0.0 (i.e. OFF), 0.5 to 100.0 seconds in

0.5-second increments.

Input Resolution:

14 bits approximately; always at least four

times better than display resolution.

Input Impedance:

Greater than 100M

resistive.

Isolation:

Universal input isolated from all outputs

except SSR at 240V AC.

Process Variable Offset:

Adjustable

±

input span.

Thermocouple: Ranges selectable from front panel:

A-1

S075-A

PM-0075

Type

Input Range

Dislayed Code

Type

Input Range

Displayed Code

R

0 - 1650

°

C

1127

J

32 - 1401

°

F H

1420

R

32 - 3002

°

F

1128

T

-200 - 262

°

C

1525

S

0 - 1649

°

C

1227

T

-328 - 503

°

F

1526

S

32 - 3000

°

F

1228

T

0.0 - 260.6

°

C

1541

J

0.0 - 205.4

°

C

1415

T

32.0 - 501.0

°

F

1542

J

32.0 - 401.7

°

F

1416

K

-200 - 760

°

C

6726

J

0 - 450

°

C

1417

K

-328 - 1399

°

F

6727

J

32 - 842

°

F

1418

K

-200 - 1373

°

C

6709

J

0 - 761

°

C *

1419

K

-328 - 2503

°

F

6710

* Default (not North America)

Continued overleaf.......

H

Default (North America)