Operating Conditions
Ambient Temperature
(Operating):
0
°
C to 55
°
C
Ambient Temperature
(Storage):
–20
°
C to 80
°
C
Relative Humidity:
20% - 95% non-condensing
Supply Voltage:
90 - 264V AC 50/60Hz (standard)
20 - 50V AC 50/60Hz or 22 - 65V DC
(option)
Source Resistance:
1000
Ω
maximum (thermocouple)
Lead Resistance:
50
Ω
per lead maximum balanced (Pt100)
Performance Under Operating Conditions
Temperature Stability:
0.01% of span/
°
C change in ambient
temperature.
Cold Junction
Compensation
(thermocouple Only):
Better than
±
1
°
C.
Supply Voltage Influence:
Negligible.
Relative Humidity
Influence:
Negligible
Sensor Resistance
Influence:
Thermocouple 100
Ω
: <0.1% of span error
Thermocouple 1000
Ω
: <0.5% of span error
RTD Pt100 50
Ω
/lead: <0.5% of span error
A.12
COMMUNICATIONS
Type:
Serial asynchronous UART-to-UART link.
Presentation Layer:
MODBUS RTU or ASCII, selectable.
Data Format:
MODBUS RTU - One start bit, odd/even/no
parity, eight-bit data one stop bit.
ASCII - One start bit, even parity, seven-bit
data, one stop bit.
Physical Layer:
RS485.