West Control Solutions N6600 User Manual
Page 19
O075-3
3-3
PM-0075
Parameter
Legend
Adjustment Range
Default
Recorder Output
Scale Max.
−
1999 to 9999
Range Max.
Recorder Output
Scale Min.
-1999 to 9999
Range Min.
Output 1 Power Limit
1
0 to 100% of full power
100%
Output 1 Cycle Time
0.5, 1, 2, 4, 8, 16, 32, 64, 128,
256 or 512 seconds
32seconds
Output 2 Cycle Time
0.5, 1, 2, 4, 8, 16, 32, 64, 128,
256 or 512 seconds
32seconds
Process High Alarm 1
value
3
Range Min. To Range Max.
Range Max.
Process Low Alarm 1
value
3
Range Min. To Range Max.
Range Min.
Band Alarm 1 value
3
0 to span from Setpoint
5 units
Deviation Alarm 1
value
3
±span from Setpoint
5 units
Alarm 1 Hysteresis
1 - 250 units
1 unit
Process High Alarm 2
value
3
Range Min. To Range Max.
Range Max.
Process Low Alarm 2
value
3
Range Min. To Range Max.
Range Min.
Band Alarm 2 value
3
0 to span from Setpoint
5 units
Deviation Alarm 2
value
3
±span from Setpoint
5 units
Alarm 2 Hysteresis
1 - 250 units
1 unit
Heater Current High
ScaleLimit
10.0A to 20.0A in 0.1A steps
21A to 100A in 1A steps
50A
Heater Current
Nominal
9
0 to Heater Current High
Scale Limit
High Scale
Limit
Low Heater Break
Alarm level (% or
amount below
nominal heater
current)
1% to 100% (of nominal) and
0 (OFF) or 0.1A/1A to Heater
Current High Scale Limit
20% or 0 (OFF)
Table 3-1 (Cont.) Set Up Parameters