DUAL SETPOINT/QUICK TRANSFER SELECTION INPUT

(OPTION)

Type:

Voltage-free or TTL-compatible

Voltage-Free Operation:

Connection to contacts of external

switch/relay; contacts open = Setpoint 1

selected (min. contact resistance =

5000

), contacts closed = Setpoint 2

selected (max. contact resistance = 50

).

TTL levels:

To select Setpoint 1: –0.6V to 0.8V

To select Setpoint 2: 2.0V to 24.0V

Maximum Input Delay

(OFF-ON):

1 second

Minimum Input Delay

(ON-OFF):

1 second

A.3

HEATER CURRENT INPUT

Input Sampling Method:

Delta-Sigma at 1kHz.

Input Resolution:

8 bits over 250ms rolling window

10 bits over 1s rolling window

Isolation:

Via external current transformer.

Internal Burden

15

Primary Input Range

Maximum:

Adjustable 10.0A - 20.0A rms in 0.1A

increments, 21A - 100A rms in 1A

increments.

Primary Input Range

Minimum:

Fixed at 0A.

Secondary Input Span:

0 - 50mA rms (assuming sinusoidal input

current waveform).