1 - 9999 increments per hour or 0 (ramping OFF). The decimal point position is as

for the input range.

4.4.4.3 SETPOINT HIGH LIMIT - Word Parameter 22

This word parameter may be modified/interrogated. It defines the maximum value

which may be assigned to the setpoint. The default value is Input Range

Maximum. The permissible range is between the current setpoint value and Input

Range Maximum. The decimal point position is as for the input range.

4.4.4.4 SETPOINT LOW LIMIT - Word Parameter 23

This word parameter may be modified/interrogated. It defines the minimum value

which may be assigned to the setpoint. The default value is Input Range Minimum.

It may be set to a value between Input Range Minimum and the current value of

the setpoint. The decimal point position is as for the input range.

4.4.4.5 CONTROL SETPOINT - Word Parameter 21

This Read Only word parameter is the setpoint value being used by the Controller

at the instant the message is received. When the setpoint is ramping, this is the

ramping setpoint value.

4.4.5 Soft Start Parameters

4.4.5.1 SOFT START SETPOINT - Word Parameter 37

This word parameter may be modified/interrogated. It defines the value of

setpoint to be used during a soft start. It may be adjusted between Input Range

Minimum and Input Range Maximum. The default value is Input Range Minimum.

4.4.5.2 SOFT START TIME - Word Parameter 38

This word parameter may be modified/interrogated. It defines the duration of the

Soft Start. It may be adjusted in 15-second increments within the range 0 (OFF) to

59 minutes 45 seconds. A value which is not an exact multiple of 15 seconds is

treated as an invalid value. The default value is 0 (OFF).

4.4.5.3 SOFT START TIME REMAINING - Word Parameter 39

This Read Only word parameter is the time remaining for a Soft Start at the instant

the message is received. When there is no Soft Start currently in effect, a value of

0 is returned.