beautypg.com

Environmental, Physical, A-12 – West Control Solutions N6600 User Manual

Page 111: A.13 environmental, A.14 physical

background image

Transmitter Drive

Capability:

32 standard RS485 unit loads

Receiver Bus Loading:

1

4

standard RS485 unit load

Baud rate:

Selectable from front panel to be 1200,

2400, 4800 or 9600 Baud.

Zone Address Select:

MODBUS RTU: Selectable from front panel in

the range 1 - 128 (standard RS485) or 1 -

255 (enhanced RS485) plus 0 (broadcast).

ASCII: Selectable from front panel in the

range 1 - 99 (for both standard RS485 and

enhanced RS485).

A.13

ENVIRONMENTAL

Operating Conditions:

See PERFORMANCE.

Approvals:

CE, UL pending, ULC pending.

EMI Susceptibility:

Certified to EN50082-1:1992 and

EN50082-2:1995.

NOTE: For line-conducted disturbances

induced by RF fields (10V 80% AM 1kHz),

the product is self-recoverable in the

frequency band 0.15 - 80MHz.

EMI Emissions:

Certified to EN50081-1:1992 and

EN50081-2:1994.

Safety Considerations:

Complies with EN61010-1:1993.

Supply Voltage:

90 - 264V AC 50/60Hz (standard)

20 - 50V AC 50/60Hz or 22 - 65V DC

(option)

Power Consumption:

4 watts approximately.

Front Panel Sealing:

To IP66 (similar to NEMA 4).

A.14

PHYSICAL

Dimensions:

Depth - 110mm

Front Panel:

Width - 48mm, Height - 48mm (

1

16

-DIN)

Width - 48mm, Height - 96mm (

1

8

-DIN)

S075-A

A-12