Environmental, Physical, A-12 – West Control Solutions N6600 User Manual
Page 111: A.13 environmental, A.14 physical
Transmitter Drive
Capability:
32 standard RS485 unit loads
Receiver Bus Loading:
1
4
standard RS485 unit load
Baud rate:
Selectable from front panel to be 1200,
2400, 4800 or 9600 Baud.
Zone Address Select:
MODBUS RTU: Selectable from front panel in
the range 1 - 128 (standard RS485) or 1 -
255 (enhanced RS485) plus 0 (broadcast).
ASCII: Selectable from front panel in the
range 1 - 99 (for both standard RS485 and
enhanced RS485).
A.13
ENVIRONMENTAL
Operating Conditions:
Approvals:
CE, UL pending, ULC pending.
EMI Susceptibility:
Certified to EN50082-1:1992 and
EN50082-2:1995.
NOTE: For line-conducted disturbances
induced by RF fields (10V 80% AM 1kHz),
the product is self-recoverable in the
frequency band 0.15 - 80MHz.
EMI Emissions:
Certified to EN50081-1:1992 and
EN50081-2:1994.
Safety Considerations:
Complies with EN61010-1:1993.
Supply Voltage:
90 - 264V AC 50/60Hz (standard)
20 - 50V AC 50/60Hz or 22 - 65V DC
(option)
Power Consumption:
4 watts approximately.
Front Panel Sealing:
To IP66 (similar to NEMA 4).
A.14
PHYSICAL
Dimensions:
Depth - 110mm
Front Panel:
Width - 48mm, Height - 48mm (
1
16
-DIN)
Width - 48mm, Height - 96mm (
1
8
-DIN)
S075-A
A-12
PM-0075