4.4.6 Alarm Parameters

4.4.6.1 ALARM 1 VALUE - Word Parameter 13

This word parameter may be modified/interrogated. It defines the level at which

Alarm 1 will go active. The decimal point position is as for the input range.

4.4.6.2 ALARM 1 HYSTERESIS - Word Parameter 35

This word parameter applies a hysteresis band on the "safe" side of the Alarm 1

value. Thus, Alarm 1 will become active when the Alarm 1 value is exceeded;

Alarm 1 will become inactive when the process variable value is outside the

hysteresis band on the “safe” side of the Alarm 1 value. Alarm 1 Hysteresis may be

set to a value in the range 1 - 250 or 0.1 - 25.0 (as per Heater Current High Scale

Limit). The effect of the hysteresis value on the operation of the different types of

alarm is illustrated in Figure 3-3.

4.4.6.3 ALARM 2 VALUE - Word Parameter 14

This word parameter may be modified/interrogated. It defines the level at which

Alarm 2 will go active. The decimal point position is as for the input range.

4.4.6.4 ALARM 2 HYSTERESIS - Word Parameter 36

This word parameter applies a hysteresis band on the “safe” side of the Alarm 2

value. Thus, Alarm 2 will become active when the Alarm 2 value is exceeded;

Alarm 2 will become inactive when the process variable value is outside the

hysteresis band on the “safe” side of the Alarm 2 value. Alarm 2 Hysteresis may be

set to a value in the range 1 - 250 or 0.1 - 25.0 (as per Heater Current High Scale

Limit). The effect of the hysteresis value on the operation of the different types of

alarm is illustrated in Figure 3-3.

4.4.6.5 LOW HEATER BREAK ALARM VALUE - Word Parameter 31

This word parameter defines a heater current value below which the Low Heater

Break Alarm will become active. It may be adjusted in the following ranges below

the Heater Nominal Current:

If Heater Break Alarm Strategy = Percentage Mode:

0 - 100% of

Heater Nominal Current (0 = OFF - value display blank, Low Heater

Alarm forced inactive). Default value = 20% below heater nominal

current. Hysteresis is half the Low Heater Break Alarm value.

If Heater Break Alarm Strategy = Absolute Mode:

0.1A/1A

(dependent upon display resolution) - Heater Current High Scale

Limit and 0 (OFF) - value display blank, Low Heater Alarm forced

inactive. Default value = 0 (OFF). Hysteresis is 0.5A for 0.1A resolution

and 2A for 1A resolution.