4.4.2.6 RECORDER OUTPUT MINIMUM VALUE - Word Parameter 28

This word parameter may be modified/interrogated. It defines the minimum scale

value for the Controller’s Recorder Output and may be adjusted within the range

–1999 to 9999. This value corresponds to the Input Scale Minimum and the

decimal point position will always be the same as that for the input. If this

parameter is set to a value greater than the Recorder Output Maximum Value, the

sense of the Recorder Output is reversed.

4.4.3 Heater Current Parameters

4.4.3.1 HEATER CURRENT HIGH SCALE LIMIT - Word Parameter 29

This word parameter defines the full scale value for the heater currrent range. It

may be adjusted from 10.0A to 20.0A in 0.1A increments, and then from 21A to

100A in 1A increments. The default value is 50A. Heater current range minimum is

fixed at •0A.

NOTE: If this parameter value is changed, the Heater Nominal

Current, Low Heater Break Alarm Value and High Heater Break Alarm

Value parameters are set to their default values.

4.4.3.2 HEATER NOMINAL CURRENT - Word Parameter 30

This word parameter defines a nominal value for the heater current. It may be

adjusted in the range 0A to Heater Current High Scale Limit value. The default

value is the Heater Current High Scale Limit value. This parameter is accessible

only if Heater Break Alarm Strategy is configured to Percentage Mode.

4.4.3.3 HEATER CURRENT - Word Parameter 33

This Read Only word parameter indicates the most recent valid heater current

value at the instant the message is received; it is equivalent to calling up the

heater current display from the front panel.

4.4.4 Setpoint Parameters

4.4.4.1 SETPOINT VALUE - Word Parameter 2

This word parameter may be modified/interrogated. It can be set to any value

between Setpoint High Limit (see Subsection 4.4.4.3) and Setpoint Low Limit (see

Subsection 4.4.4.4). When the setpoint is ramping, this is the target setpoint value.

4.4.4.2 SETPOINT RAMP RATE - Word Parameter 24

This word parameter may be modified/interrogated. It defines the rate at which

the current setpoint can be made to ramp and can be set to a value in the range