Output 1 power limit - word parameter 20, Output 1 cycle time - word parameter 10, Output 2 cycle time - word parameter 19 – West Control Solutions N6600 User Manual

Page 47: Recorder output maximum value - word parameter 27

background image

Manual control is not selected, this word parameter is Read Only; if Manual

control is selected, this parameter may be adjusted.

4.4.2.2 OUTPUT 1 POWER LIMIT - Word Parameter 20

This word parameter may be modified/interrogated. It defines the power limit for

Output 1 and may be set in the range 0% to 100% of full power. The default value

is 100%. The decimal point position is fixed at 1 decimal place. If Soft Start is used,

this power limit is applicable only during Soft Start. When Soft Start is completed,

Output 1 power can go to 100%.

4.4.2.3 OUTPUT 1 CYCLE TIME - Word Parameter 10

This parameter may be modified/interrogated. The value to which this is set is

dependent upon the output type and the nature of the process to be controlled.

For relay outputs, this parameter should be set to as large a value as possible

(consistent with satisfactory control of the process) in order that the life of the relay

be maximised. For SSR Drive and Solid State outputs, lower values may be used.

The decimal point position is set at 1 decimal place.

NOTE: Cycle Time values must be written correctly i.e. the value must

be a power of 2 in the range 0.5 - 512 (0.5, 1, 2, 4, 8, etc.).

4.4.2.4 OUTPUT 2 CYCLE TIME - Word Parameter 19

This parameter may be modified/interrogated. The value to which this is set is

dependent upon the output type and the nature of the process to be controlled.

For relay outputs, this parameter should be set to as large a value as possible

(consistent with satisfactory control of the process) in order that the life of the relay

be maximised. For SSR Drive and Solid State outputs, lower values may be used.

The decimal point position is set at 1 decimal place.

NOTE: Cycle Time values must be written correctly i.e. the value must

be a power of 2 in the range 0.5 - 512 (0.5, 1, 2, 4, 8, etc.).

4.4.2.5 RECORDER OUTPUT MAXIMUM VALUE - Word Parameter 27

This word parameter may be modified/interrogated. It defines the maximum value

for the Controller’s Recorder Output and may be adjusted within the range –1999

to 9999. This value corresponds to the Input Scale Maximum and the decimal

point position will always be the same as that for the input.

NOTE: If this parameter is set to a value less than the Recorder

Output Minimum Value, the sense of the Recorder Output is

reversed.