process being controlled. The Setpoint Low Limit may be adjusted between the

Input Range Minimum and the current setpoint value. The default value is Input

Range Minimum.

3.2.14 Recorder Output Scale Maximum

This parameter defines the value of process variable or setpoint (whichever is

applicable) at which the Recorder Output reaches its maximum value; for

example, for a 0 - 5V Recorder Output, this value corresponds to 5V. It may be

adjusted within the range –1999 to 9999. The decimal point position for the

Recorder Output is always the same as that for the process variable input range.

The default value is Input Range Maximum. This parameter is not applicable if the

Recorder Output option is not fitted.

NOTE: If this parameter is set to a value less than that for the Recorder

Output Scale Minimum (see Subsection 3.2.15), the relationship between

the process variable/setpoint value and the Recorder Output is reversed.

3.2.15 Recorder Output Scale Minimum

This parameter defines the value of the process variable or setpoint (whichever is

applicable) at which the Recorder Output reaches its minimum value; for

example, for a 0 - 5V Recorder Output, this value corresponds to 0V. It may be

adjusted within the range –1999 to 9999. The decimal point position for the

Recorder Output is always the same as that for the process variable input range.

The default value is Input Range Minimum. This parameter is not applicable if the

Recorder Output option is not fitted.

NOTE: If this parameter is set to a value greater than that for the Recorder

Output Scale Maximum (see Subsection 3.2.14), the relationship between

the process variable value and the Recorder Output is reversed.

3.2.16 Output 1 Power Limit

This parameter is used to limit the power level of Output 1 and may be used to

protect the process being controlled. If no protection is required, this parameter

may be set to 100% (the default value). It may be adjusted between 0% and

100%. This parameter is not applicable if Proportional Band 1 is set to 0.

If Soft Start is used, this power limit is applicable ony during Soft Start. When Soft

Start is completed, Output 1 power can go to 100%.

3.2.17 Output 1 Cycle Time

The cycle time value required is dependent upon the process being controlled

and the type of output being used for Output 1. For a Relay Output, the cycle

time should be as large as possible (whilst remaining compatible with the process

O075-3