8.3

Replacing the complete electronic unit of the IFC 110 PF signal converter

Switch off the power supply before opening the housing.

1) Remove the cover from the terminal compartment (remove 2 screws).
2) Pull all cables out of the plug-in terminals.
3) Remove the glass cover from the control compartment (remove 4 screws).
4) Remove 4 screws from the front panel F, take hold of the handle on the upper end of the front panel and carefully pull out

the complete electronic unit of the signal converter housing.

5) Carefully remove the data EEPROM IC14 (on ADC printed circuit board) from the old electronic unit and move it to

the new electronic unit. Observe the direction of the IC when plugging the data EEPROM. After changing the EEPROM
from the old to the new electronic unit, no further adjustments or settings are required. Refer to the drawing on this page
and to the illustrations of the printed circuit boards in sect. 8.5.

6) Re-assemble in reverse order (items 4 – 1 above).

ADC

printed circuit board of A/D converter (ADC)

NT

printed circuit board for power unit

BDE

motherboard

OP

connection plug for additional modules

F

front panel

PL

MP

5-pin plug connector for connection of the printed

F1

power supply fuse, see Sect. 8.1 and 9.

circuit board MP for the magnetic sensors

FSV

printed circuit board for field current supply

S

7 nuts for fastening the electronic unit to front panel

H

3 retaining clips at the back of the front panel

S

LP

screws for fastening the PCB’s

IC14

data EEPROM (8-pin)

S

MP

nut and special steel tooth lock washer for fixing the

I/O

printed circuit board for outputs and inputs

MP PCB for the magnetic sensors

MP

printed circuit board for magnetic sensors