beautypg.com

KROHNE TIDALFLUX IFM 4110 PF EN User Manual

Page 33

background image

7.30830.32.00

33

Setting of totalizer format

Auto (exponent notation)

# . # # # # # # #

# # # # # . # # #

# # . # # # # # #

# # # # # # . # #

# # # . # # # # #

# # # # # # # . #

# # # # . # # # #

# # # # # # # #

Select with

↑ and ↓ keys.

Press

↵ key to change to subfunction “DISP. MSG.”.

→ DISP. MSG. = additional messages desired in measuring mode , press → key

NO

no additional messages

YES

display additional messages, e.g. errors, in sequence with measured values)

Select with

↑ and ↓ keys.

Press

↵ key to change to subfunction “DISP.LEVEL”.

→ DISP.LEVEL = measured relative level desired in measuring mode , press → key

NO

no display

YES

display measured relative height, in sequence with measured values

Select with

↑ and ↓ keys.

Press

↵ key to return to Fct. 1.04 DISPLAY

Note: “BUSY” is displayed in measuring mode when all displays are set to “NO DISP.” or “NO”.
Sequencing of displays is automatic. In measuring mode, however, keys

and

can be used for manual sequencing. Return

to automatic sequencing after approx. 3 minutes.

Please refer to Section 2.5.7 “Standard factory settings”

5.5

Internal electronic counter

The internal electronic totalizer counts in m

3

regardless of the unit set in Fct. 1.04, subfunction “DISP. FLOW”.

The counting range depends on the meter size and has been selected such that the totalizer will count for at least 1 year
without overflow.

Meter size

Counting range

DN mm

inch

in m

3

US Gal equivalent

200

8

0 – 9 999 999.9999999

0 – 2 641 720 523.5800

250 – 600

10 – 24

0 – 99 999 999.9999999

0 – 26 417 2050235.800

Only a part of the totalizer count is shown in the display as it is not possible to display a 14-digit number. Unit and format of
the display are freely selectable. Refer to Fct. 1.04, subfunction “DISP.TOTAL.” and sect. 5.4 to determine which part of
the count is to be displayed. Display overflow and totalizer overflow are independent of one another.

Example

Internal count

0000123.7654321 m

3

Format, display unit

XXXX.XXXX

liter

Internal count in unit

0123765.4321000 liter

Displayed

3765.4321

liter