7.30830.32.00

28

Fct.

Text

Description and settings

3.0

INSTALL.

Installation menu

3.01

LANGUAGE

Select language for display texts

GB / USA (English)

F (French)

D (German)

Press

↵ key to return to Fct. 3.01 “LANGUAGE”.

3.02

FLOWMETER

Set data for primary head

→ DIAMETER

Select size from meter size table
DN 2.5 – 3000 mm (1/10 – 120 inch)
Select with

↑ key.

Press

↵ key to change to subfunction “FULL SCALE”.

→ FULL SCALE

Full-scale range for flow Q

100%

.

To set, refer to Fct. 1.01 “FULL SCALE”.
Press

↵ key to change to subfunction “GK VALUE”.

→ GK VALUE

Set primary constant GK
See instrument nameplate of primary head.
Range:

1.0000 – 9.9999

Press

↵ key to change to subfunction “FIELD. FREQ.”.

→ FIELD FREQ..

Magnetic field frequency
Values: 1/2, 1/6, 1/18 and 1/36 of power frequency, see instrument nameplate.
Press

↵ key to change to subfunction “FLOW DIR.”.

On DC instruments change to subfunction “LINE FREQ.”.

→ LINE FREQ..

Power frequency customary in the country where the instrument is used
Please note: this function to suppress line frequencies interferences is limited to instruments with
DC supply unit (24 V DC).
Value: 50 Hz and 60 Hz.
Press

↵ key change to subfunction “FLOW DIR.”.

→ FLOW DIR.

Define flow direction (in F/R mode: forward flow).
Set according to direction of arrow on primary head:

+ DIR.

- DIR.

Select using

key.

Press

↵ key to return to Fct. 3.02 “FLOWMETER”.

3.03

ZERO SET

Zero calibration
Note: Carry out only at “0” flow and with completely filled measuring tube!
Precautionary query:

CALIB. NO

Press

↵ key to return to Fct. 3.03 “ZERO SET”.

CALIB. YES

Press

↵ key to start calibration.

Duration approx. 15-90 s (depending on magnetic field frequency), current
flow rate displayed in the selected unit (s. Fct. 1.04 “DISP. FLOW”).

A “WARNING” sign appears when flow rate “>0”; acknowledge by pressing

↵ key.

STORE NO

do not store new zero value

STORE YES

store new zero value

Select using

↑ key.

Press

↵ key to return to Fct. 3.03 “ZERO SET”.

3.04

ENTRY CODE

Entry code required to enter setting mode?

NO

entry with

key only

YES

entry with

key and Code 1:

Press

↵ key to return to Fct. 3.04 “ENTRY CODE”.

3.05

USER UNIT

Set any required unit for flow rate and counting

→ TEXT VOL.

Set text for required flow rate unit (max. 5 characters)
Factory setting = Liter or US Mgal
Characters which can be assigned to each place:

A-Z, a-z, 0-9 or “-“ (=blank character)

Press

↵ key to transfer to subfunction “FACT. VOL.”.

→ FACT. VOL.

Set conversion factor F

M

for volume

Factory setting “1.00000 E+3” for “Liter” or “2.64172 E-4” for “US MGal”
(exponent notation, here 10

3

or 2.64172 x 10

-4

)

Factor F

M

= volume per 1 m

3

.

Setting range

1.00000 E-9 to 9.99999 E+9 (=10

-9

to 10

+10

)

Press

↵ key to transfer to subfunction “TEXT TIME”.

→ TEXT TIME

Set text for any time (max. 3 characters)
Factory settings = “hr” (hours)
Characters which can be assigned to each place:

A-Z, a-z, 0-9 or “-“ (=blank character).

Press

↵ key to transfer to subfunction “FACT. TIME”

→ FACT. TIME

Set conversion factor F

T

for time

Factory setting “3.60000 E+3” for “hr” (exponent notation, here 3.6 x 10

3

).

Set factor F

T

in seconds.

Setting range

1.00000 E-9 to 9.99999 E+9 (=10

-9

to 10

+10

)

Press

↵ key to return to Fct. 3.05 “USER UNIT”.

3.06

APPLICAT.

Set modulation range of A/D converter

→ FLOW

STEADY (150% of Q

100%

)

PULSATING (1000% of Q

100%

)

For partly filled flowmeters, this option should always be set to “PULSATING” !
Press

↵ key to change to subfunction “ADC GAIN”.