7.30830.32.00

44

5.19

Limit switches

Fct. 1.07 – 1.10 Status outputs A1, A2, D1 and D2
(Define operating mode of output terminals A1, see sect. 5.18)
Press

→ key

Press

↑ key as often as required to set one of the status outputs to “TRIP. POINT”

Press

→ key to change to option flow direction:

Select:

+ DIR.

- DIR.

2 DIR.

Select with

↑ or ↓ keys, press ↵ key to confirm and to change to numerical setting, 1st number (cursor) flashes.

Change flashing number (cursor) with keys

↑ and ↓. Use ← and → keys to shift cursor 1 place to left or to right.

Display:XXX – YYY
Setting ranges:
XXX value: 0 – 150% of Q

100%

.

YYY value: 0 – 150% of Q

100%

.

hysteresis

1% (=difference between XXX and YYY values)

Switching behavior (NO / NC contact) and hysteresis are adjustable

Normally Open (NO) contact

Normally Closed (NC) contact

XXX value > YYY value

XXX value < YYY value

Switch closes when flow exceeds XXX value

Switch opens when flow exceeds YYY

value

Example:

XXX = 55%

Example:

XXX = 45%

YYY = 45%

YYY = 55%

hysteresis = 10%

hysteresis = 10%

Please note:

If two status outputs (e.g. D1 and D2) are activated it is possible to
have e.g. min. and max. values signaled.

5.20

Range change

Automatic range change by status output

Fct. 1.07 – 1.10 Status outputs A1, A2, D1 and D2
(Define operating mode of output terminal A1, see Section 5.18)

Press

→ key

Press

↑ key as often as required to set one of the status outputs to automatic range change “AUTO. RNG.”.

Press

↵ key to change to numerical setting, 1st number (cursor) flashes.

Change flashing number (cursor) with keys

↑ and ↓. Use ← and → keys to shift cursor 1 place to left or to right.

Flashing numbers (cursor) can also be directly set with the 10-key keyboard.

Setting range:

5 – 80 PERCENT of Q

100%

(=low to high range ratio 1:20 to 1:1.25)

YYY XXX

hysteresis

45% 55%
Q

XXX YYY

hysteresis

45% 55%
Q