beautypg.com

KROHNE TIDALFLUX IFM 4110 PF EN User Manual

Page 54

background image

7.30830.32.00

54

Group P

Faults / Symptoms

Cause

Remedial action

Wrong connection / polarity

Connect properly, see sect.
2.5.3 and 2.5.6, note
recommended resistances !

Totalizer or external voltage
source defective

Check connections, totalizer and
external voltage source and
replace if necessary.

Internal power supply (E+ E-) is
voltage source, shorted or
defective pulse output

Check connections and cables,
see sect. 2.5.3 and 2.5.6.
Voltage between E+ and E-
approx. 24 V. If voltage is a lot
smaller, switch off the
instrument, eliminate the short
circuit and replace fuses F1 and
F8 on the I/O PCB if necessary.
Switch the instrument back on.
If it still does not operate, pulse
output is defective. Replace I/O
PCB or complete electronic unit,
see sect. 8.3 and/or 8.4.

Pulse output switched off or
wrong flow direction setting

Switch on pulse output and
change flow, see sect. 5.8 and
5.13, Fct. 1.06 (P), 1.07 (A1)
and 3.02.

Fatal error, red LED is on

Replace signal converter or
consult Krohne Service, having
first noted down hardware
information and error status. see
sect. 7.3, Fct. 2.02

Totalizer connected but does
not count pulses

Control input C1 or C2 is set to
“Zero outputs” and is activated

Change settings, see sect. 5.10,
Fct. 1.11 and 1.12 or deactivate
control input.

Terminals A1 and A

are not

defined as a 2nd pulse output

Switch on in Fct. 3.07 and set in
Fct. 1.07.

P1

These causes only apply to the
2nd pulse output P2, terminal
A1 !

Resistance of totalizer too low for
DC operation, I > 100 mA.

Re-position jumper X4 on I/O
PCB to suit DC operation, see
sect. 6.3.

P2

Constant output of totalizer
pulses

Control input C1 or C2 is set to
“Hold outputs” and is activated

Change setting, see sect. 5.10,
Fct. 1.11 and 1.12 or deactivate
control input.

P3

Unsteady pulse rate

Electrical conductivity of process
liquid is too low

Increase time constant (see
Sect. 6.5-6.7) or consult Krohne
Service.

P4

Pulse rate too high or too low

Incorrect pulse output settings

Correct settings in Fct. 1.06 (P)
or 1.07 (A1).