KROHNE TIDALFLUX IFM 4110 PF EN User Manual

Page 39

background image

7.30830.32.00

39

Select with

↑ and ↓ keys.

Press

↵ key to return to Fct. 3.01 LANGUAGE.

5.12

Entry code

Fct. 3.04 ENTRY CODE
Press

→ key

Select

NO

no code, enter programming mode by pressing

key.

YES

enter programming mode by pressing

key and Code 1:

.

Select with

↑ and ↓ keys.

Press

↵ key to return to Fct. 3.04 ENTRY CODE.

5.13

Primary head

Fct. 3.02 FLOW METER
Press

→ key

→ DIAMETER = set meter size (see instrument nameplate), press → key
Select size from table of meter sizes:
DN 2.5 – 3000
equivalent to 1/10 – 120 inch

Select with

↑ and ↓ keys.

Press

↵ key to change to subfunction “FULL SCALE”.

→ FULL SCALE = set full scale range, press → key
Set as described in sect. 5.1.

Press

↵ key to change to subfunction “GK VALUE”.

Please note that if “VALUE P” or “VALUE P2” is displayed after pressing

↵ key:

PULSE/VOL. is set in Fct. 1.06 PULS P and/or in Fct. 1.07 PULS 2 A1, subfunction “SELECT P” and/or “SELECT P2”.
Due to the changed full-scale range Q

100%

, the output frequency (F) of the pulse outputs is either exceeded or not reached:

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Change pulse value accordingly, see sect. 5.08 Pulse output P, Fct. 106 and/or 2nd pulse output A1, Fct. 1.07.

→ GK VALUE = set primary head constant GK, press → key

1.0000 – 9.9999

note information on instrument nameplate, do not change setting

Change flashing number (cursor) with keys

↑ and ↓. Use ← and → keys to shift cursor 1 place to left or right.

Flashing numbers can also be directly set with the 10-key keyboard.
Press

↵ key to change to subfunction “FIELD FREQ.”.

→ FIELD FREQ. = set magnetic field frequency, press → key

1/2

1/6

(1/2, 1/6, 1/18 or 1/36 of power frequency, see instrument nameplate,

1/18

1/36

do not change setting.

Select with

↑ and ↓ keys.

Press

↵ key to change to subfunction “FLOW DIR.”.

(for DC instruments change to subfunction “LINE FREQ.”).