7.30830.32.00

37

5.9

Status outputs A1 / A2 and D1 / D2

PLEASE NOTE:
Connection diagrams see sect. 2.5.6.
Status outputs

A1

A2

D1

D2

Select Fct. _ . _ _
then press

key

1.07

1.08

1.09

1.10

Terminals

A1 / A

A2 / A

D1 / D

D2 / D

Max. switching
current

100 mA (AC or DC)

200 mA (DC polarized)

see sect. 6.3

100 mA (AC or DC)

100 mA (AC or DC)

100 mA (AC or DC)

Remark

“STATUSOUTP.” must
be selected in Fct. 3.07
HARDWARE,
subfunction
“TERMINALS”.

-

-

-

PLEASE NOTE:

Select function for status outputs, press

→ key

ALL ERROR

indicate all errors

FATAL.ERROR

only indicate fatal errors

OFF

switched off, no function

ON

signals the operation of the flowmeter

SIGN I

F/R mode

SIGN P/P2

F/R mode

OVERFL. I

Exceeding output ranges

OVERFL. P/P2

Exceeding output ranges

INVERS. A1

switches output A2 inverse to A1. A1 and A2 then operate as change-over elements with common
centre grounding contact A

. Only available when status output is selected in Fct. 3.07 “TERM.

A1”.

INVERS. D1

switches output D2 inverse to D1. D1 and D2 then operate as change-over elements with common
centre grounding contact D

.

EMPTY PIPE

signals that measuring tube is empty, only with option “empty tube detection”

AUTO. RNG.

Automatic range change. Setting range 5 – 80 PERCENT (=high to low ratio, 1:20 to 1:25, value

must be higher than that of Fct. 1.03 L.F. CUTOFF).

FULL SCALE

Select flow direction (characteristic) for full-scale range

+ DIR.

- DIR.

2 DIR.

Select with

↑ and ↓ keys.

Define full-scale range
XXX - YYY
0-150%

0-150%

normally open contact: XXX > YYY
normally closed contact:

XXX < YYY

hysteresis:

difference between XXX and YYY

Press

→ key to change to numerical setting, 1st number (cursor) flashes.

Change flashing number (cursor) with keys

↑ and ↓. Use ← and → keys to shift cursor 1 place to left or right.

Flashing numbers can also be directly set with the 10-key keyboard.
Press

↵ key to return to Fct. 1.07, 1.08, 1.09 and 1.10 for status outputs A1, A2, D1 and D2.