Terminating set up menu -24, Setup=display, Auto interval=2 – Yokogawa DR240 User Manual
Page 185: Auto intvl set*** setup=abort, Display end, Set up
![background image](/manuals/360331/185/background.png)
10-24
IM DR232-01E
10.10 Selecting Display Update Interval, Registering
Details Set/Selected with SET UP Menu, and
Terminating SET UP Menu
D I S P
M O D E
P R I N T
F U N C
I N S
D E L
R A N G E A L A R M
S E T
C H A R T
E N T E R
F E E D
M. F U N C 1
M. F U N C 2
RECORD
ALARM
CHART
KEYLOCK
R E C O R D
SETUP=DISPLAY
↓
COLOR LOCK FUNC_PARM SET_PARM DISPLAY
↑
>Select Setting Parameter
E S C
• Enter the SET UP menu in the following procedure:
1. When the display presents the operation display mode or a menu other than the SET UP
menu, first turn off the power switch.
2. Turn the switch back on while pressing the DISP key and continue pressing the DISP key
for about 5 seconds.
• Select/set
using the
keys.
• If exiting the following lower menu setting halfway, press the MODE (ESC) key. The display
returns to the main menu to which the lower menu belongs. However, newly set or selected
contents are canceled.
• When setting proceeds to the display for the setting end, the newly set or selected contents are
established.
AUTO INTERVAL=2
>2 3 4 5
***AUTO INTVL SET***
SETUP=ABORT
ABORT STORE
DISPLAY
END
ENTER
ESC
ENTER
ENTER
ESC
ENTER
( S E T U P e n d )
( M a i n m e n u )
( L o w e r m e n u )
SET UP=
Selection of Display Update Period (DISPLAY)
Select the display update interval when the operation display mode in the display is AUTO.
• Select 2, 3, 4, or 5 seconds.
• The default setting is 2 seconds.
Registration/Abortion of Setting/Selection Details and Termination of SET UP
menu (END)
In order to make the details set/selected in the SET UP menu effective, a registering operation is
necessary. In contrast, the status can also be brought to that before setting/selection (abort)
without registration. Terminate the SET UP menu after registering or aborting operation.
• ABORT: Registration is aborted and the SET UP menu is terminated.
• STORE: After registration, the SET UP menu is terminated.
• The default setting is ABORT.
Select the END menu, then press the ENTER key. The operation display mode is reached about