Communications baud rate, Allen bradley protocol, Ac line frequency – Watlow MLS User Manual
Page 79
Setup
MLS User’s Guide 67
Communications Baud Rate
Use this menu to set the Communications Baud Rate to 2400 or 9600
baud.
Selectable values:
9600 or 2400.
NOTE
If you use ANASOFT, be sure to set ANAINSTL to
the same baud rate that you set in this menu.
Allen Bradley Protocol
Use this menu to set the protocol type to either Allen Bradley or
ANAFAZE.
Selectable values:
Yes or No.
AC Line Frequency
Use this menu to configure the controller to match an AC line frequency
of 50 or 60 Hz. (This function is provided for international users who
require 50 Hz lines.) Since the controller reduces the effect of power
line noise on the analog measurement by integrating the signal over the
period of the AC line frequency, the controller's noise rejection will
suffer if the line frequency is not set correctly.
Selectable values:
60 Hz or 50 Hz.
NOTE
If you change the AC line frequency, you must switch
power to the MLS on and off for the change to take
effect.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
COMMUNICATIONS
BAUD RATE? 9600
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
ALLEN BRADLEY
PROTOCOL? NO
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
AC LINE FREQ ?
60 HERTZ