Setup

MLS User’s Guide 89

When the controller powers up or the setpoint changes, deviation alarms
do not activate until the process goes inside the deviation alarm band--
preventing deviation alarms during a cold start. (High and low process
alarms are always enabled.)

Use menus to set the following process alarm parameters for each loop:

High and low process alarm type, setpoint, and digital output.

High and low deviation alarm type, deviation alarm value, and alarm

digital output.

Alarm deadband.

Loop alarm delay.

The setpoints, deviation alarm values, and deadband all use the same
decimal format as the loop's process variable.

High Alarm Limit

Setpoint

Low Alarm Limit

SP + Deviation

SP - Deviation

}

Deadband

}

Deadband

}

Deadband

}

Deadband

High deviation alarm on

High deviation alarm off

Low deviation alarm on

Low deviation alarm off

High process alarm off

High process alarm on

Low process alarm on

Low process alarm off