Linear Scaling Examples

MLS User’s Guide 119

Linear Scaling Examples

Example 1: Configuring a Pressure Sensor

You’re using a pressure sensor that generates a 4-20 milliamp signal.
The sensor generates 4 milliamps at 0.0 PSI and 20 mA at 50.0 PSI.

Setup

You connect the sensor to a loop input set up with a resistor scaling
network to produce 60 millivolts at 20 mA. (See the

Inputs

section of

Chapter 2: Installation

for more information on scaling networks.)

The sensor measures PSI in tenths, so the appropriate display format is -
999.9 to +3000.0.

This table shows the input readings.

Based on these input readings, use these scaling values:

PV

Displayed

Sensor Input

Reading (%FS)

50.0 PSI

20

100%

0.0 PSI

4

100%x(4ma/20 ma) = 20%

Parameter

Low Value

High Value

Process Value (PV)

0.0 PSI

50.0 PSI

Input Reading (RDG)

20.0