beautypg.com

Connecting thermocouples, Rtd inputs – Watlow MLS User Manual

Page 52

background image

40 MLS User’s Guide

Installation

Connecting Thermocouples

Connect the positive T/C lead to the A+ terminal. Connect the negative
T/C lead to the A- terminal of TB1. The figure below shows a typical
thermocouple connection.

Use 20 gauge T/C extension wire for all T/C inputs.

If you use shielded wire, tie the shield to panel ground.

Install a jumper or zero ohm resistor in location RC on the AIM-TB

if it had been removed.

This figure shows a typical thermocouple connection.

RTD Inputs

The standard industrial RTD is an 100 ohm, three-wire, platinum
assembly as shown in the next figure. Watlow-Anafaze highly
recommends that you use the three-wire RTD to prevent reading errors
due to cable resistance.

If you order an RTD1, RTD2, or RTD3 configuration, we will con-

figure your MLS for the standard three-wire RTD.

If you must use a two-wire RTD, jumper A- to AUX.

If you must use a four-wire RTD, do not connect the fourth wire.

Watlow-Anafaze offers three standard DIN 385 curve RTD input
ranges, as shown in the table below:

This figure shows a typical 3-wire RTD connection.

RTD
Type

Input Range

Display

Resolution

RTD1

-100.0 to 300.0 C
-148.0 to 572.0 F

0.1 C
0.1 F

RTD2

-120 to 840 C
-184 to 1544 F

1 C
1 F

RTD3

-70 to 300 C
-94 to 572 F

1 C
1 F

White

Red

Type J T/C

IN +

IN

Shield