T/c inputs, Wiring recommendations – Watlow MLS User Manual

Page 51

background image

Installation

MLS User’s Guide 39

2. Select the # of digits and decimal point location for the full scale PV

display. The smallest possible range is -0.9999 to +3.0000; the largest
possible range is -9999 to 30000.

3. Enter the zero and full scale values (process variables) you want dis-

played when the input signal is at zero and full scale.

T/C Inputs

WARNING

Use ungrounded thermocouples (thermocouples
which have the T/C junction isolated from the
metal protection sheath). Grounded thermocou-
ples will damage the MLS if voltage between the
loops exceeds 10 volts.

If you are installing the MLS in an existing tem-
perature control system, check all grounded T/C
assemblies in the system. Make sure there is no
voltage between T/C leads.

You can connect all T/C types directly to the MLS. Watlow-Anafaze
provides J, K, T, R, S, and B type linearization and cold junction
compensation. (Other thermocouple types require custom input ranges;
contact Watlow-Anafaze for more information about them.)

Wiring Recommendations

Follow these recommendations for thermocouple wiring:

Use 18 or 20 AWG thermocouple (T/C) extension wire for all ther-

mocouple inputs.

Most T/C wire is solid unshielded wire. Use shielded wire if required

at your installation; ground one end only.

Use less than 500' of T/C extension wire. Longer wire runs exceed

accuracy and source impedance specifications.

Install T/C wiring in a separate conduit away from AC power (the

120 Vac supply) and high power (240 Vac or higher) wiring.