3-2-7 Homing
During power-up or upon alarm release, you will need to home. After selecting the position number and starting,
homing is executed first. Upon homing, homing complete output will turn ON (standard specifications). You may
not execute just homing from P I/O. In addition, in case you wish to move to the home position in normal mode,
we recommend you set the position number to where 0 was input into the position of position data, and then,
move to that position. With the absolute specifications, once home location is taught, there is no need to home
after cycling power.
3-3 Timing
Chart
ACC/DEC
Content
Minimum value
Maximum value
T1
Start ON minimum time width
6 msec
-
T2
Start OFF minimum time width
6 msec
-
T3
Start ON
Command Position hold time
6 msec
-
T4
Start ON
Positioning complete OFF delay time
- 7
msec
T5
Positioning complete OFF
ON during moving delay time
- 1
msec
T6
Hold OFF
OFF during moving delay time
- *1
T7
Hold ON
ON during moving delay time
- 6
msec
T8
During moving OFF
ON positioning complete delay time
- 2
msec
T9
Positioning complete OFF
OFF positioning complete delay time
0.1 msec
1 msec
T10
Complete position ON
Positioning complete output delay time
0.1 msec
1 msec
*2
*1: Maximum value will depend on acceleration/deceleration.
*2: To view complete position, upon positioning complete ON, please allow more time for the scan of the
sequencer.