1-6 Heat Dissipation and Mounting
The size of the controller panel, controller position and cooling method should all be designed so that the
controller boundary temperature remains under 40ºC. As the diagram below shows, mount vertically (wall
mounting). Controllers are cooled by active ventilation (brewing upward). For installation, make sure to leave
more than 100mm of space above and 50mm of space below the controller, following this direction. When
mounting with several controllers lined up, also mount an agitator fan above the controllers in order to maintain
surrounding air temperature. In addition, the spacing between the controller front side and wall (cover) should be
more than 100mm..
As for the spacing in between the controllers, whether or not it’s a single controller or multiple controllers, please
leave enough space so that controller mounting and removal may be done easily.
Direction of air
Fan