Relay Specifi cations
Hysteresis

Adjustable (absolute in

Engineering

Units)

Latch

Reset in test screen or

View

Mode

On Delay

9999.9 seconds (max)

Test Mode

Set On or Off

Maximum pulse rate:

400 pulses/minute

Volumetric Pulse Width: 0.1 s to 3200 s

Open Collector
Type:

NPN

Max. Voltage Rating:

30 VDC

Max. Current Rating:

50 mA

Dry-Contact Relays
Type:

SPDT

Form:

C

Max. Voltage Rating:

30 VDC or 250 VAC

Max. Current Rating:

5 A

Shipping Weights
Base Unit

0.63 kg (1.38 lb)

Batch Module

0.16 kg (0.35 lb)

Relay Module

0.19 kg (0.41 lb)

Standards and Approvals
CE, UL, CUL

China RoHS (visit gfsignet.com for details)

This device complies with Part 15 of the FCC

rules. Operation is subject to the following two
conditions:
(1) This device may not cause harmful
interference, and
(2) This device must accept any interference
received, including interference that may cause
undesired operation.

RoHS compliant

Manufactured under ISO 9001 for Quality,
ISO 14001 for Environmental Management and
OHSAS 18001 for Occupational Health and Safety.

Electrical Requirements
Power to Sensors:
Voltage:

+4.9 to 5.5 VDC @

25 °C, regulated

Current:

20

mA

Short Circuit

Protected

Terminal Blocks
• Pluggable screw type
• 14 AWG max wire gauge

Input Power Requirements
DC (preferred)

24 VDC Input;

range: 10.8 to

35.2 VDC regulated

300 mA maximum

Overvoltage protection 48 Volt Transient

Protection

Device

Current limiting for circuit protection
Reverse-Voltage protection

Loop Characteristics
With DC power input (preferred)
Max. loop impedance
@ 12 V loop power 250 Ω max.
@ 18 V loop power 500 Ω max.
@ 24 V loop power 750 Ω max.

Specifi cations