LOOP Menu
Loop Source
In ADVANCED Mode, select COMPLETION or FLOW RATE.
In SIMPLE Mode, only COMPLETION is available for the loop source.
mA at Completion
Shown if COMPLETION is selected. Enter mA value to be output when batch is
completed. Select 4.0 mA or 20 mA.
Error Value
Shown if COMPLETION is selected. Set desired Loop output value when sensor error
(e.g., bad sensor, broken wire) is detected. Select 3.6 mA, 22 mA, NONE. Default = 3.6.
4 mA Setpoint
Shown if FLOW RATE is selected. Set fl ow rate value corresponding to desired
4 mA output. Default = 0.
20 mA Setpoint
Shown if FLOW RATE is selected. Set fl ow rate value corresponding to desired
20 mA output. Default = 100.
Adjust 4 mA
Allows fi ne-tuning to compensate for errors in other equipment connected to the 9900.
The display value represents the precise current output. Adjustment limits: 3.80 mA to 5.00 mA.
Default = 4.00 mA.
Adjust 20 mA
Allows fi ne-tuning to compensate for errors in other equipment connected to the 9900.
The display value represents the precise current output. Adjustment limits: 19.00 mA to 21.00 mA.
Default = 20 mA.
Test Loop
Press ▲ or ▼ to manually output a current value from 3.6 mA to 21.00 mA to test the
output loop.
INPUT Menu - continued
Mode Select
Select ADVANCED or SIMPLE Mode. ADVANCED Mode enables additional features in
RELAY and LOOP Modes. Default = SIMPLE.
Count Up/Down
Select count direction of Batch Volume and Percent Complete
(Source Volume always counts down). Default = Count Up.
Note: If Count Down is selected, Dispensed volume and Source volume can display negative values.
Missing Signal?
Determines if a Batch is stopped when No Flow is detected.
If YES is selected, Batch will be stopped; if NO is selected, Batch will continue. Default = NO.
Note:
This setting is independent of Missing Signal Relay Mode; see page 19.
Set On Delay
Shown if MISSING SIGNAL is set to YES. Set desired ON delay time in seconds.
Default = 6 sec.
Select Batch Type
To change desired instrument type (i.e., Flow, pH, etc.). The bottom line will display
ALL SETTINGS WILL BE RESET. ARE YOU SURE? The top line of the display will blink NO.
Press ▼ or ▲ to select YES. Press ENTER again to fi nalize your selection.
For other 9900 instruments, BATCH will be displayed only when the Batch Module is installed.
Menu System