ERROR – Error:

If using S

3

L fl ow sensor, activates relay when no

sensor is detected.

MULTIPLE – Multiple Mode:

Activates relay when any one of the four enabled
conditions are met. User can select from Missing
Signal, Overrun, High Flow or Error.

TOT VOL – Totalizer Volume:

When resettable totalizer exceeds specifi ed volume,
relay activates and latches.
Requires Totalizer Volume Reset to deactivate relay
(see Reset Total, pg. 16).
This mode is useful to trigger a reminder when a
process is due, as for a backwash cycle or fi lter
change.

TWO STG – Two Stage:

This function is designed to prevent overfi lling or

to minimize water hammer. Both the mainline relay

and the bypass relay are energized when the batch

starts. The mainline relay then de-energizes at a

programmed batch percentage, allowing fl ow to

continue through a smaller bypass line to reduce the

fi ll rate (see diagram). After the batch is dispensed,

the bypass relay de-energizes, completing the

sequence.
NOTE:

If Relay 1 is selected for Two-Stage operation,

relay 2 defaults to Bypass. If Relay 2 is selected,

relay 3 defaults to bypass. If Relay 3 is selected,

relay 2 defaults to bypass.

flow

to tank

Bypass valve

Main line

Valve

Overflow

tank

0%

90% 100%

Relay 2 Bypass

Relay 1 Main

Time

Advanced Mode

(See Input Menu - Page 17)

Relay Mode Settings - continued

Relay energized

Relay de-energized

% Batch Percentage

Relay energized

Relay de-energized