Relay module wiring, Relay mode settings *simple mode, See input menu - page 17) – GF Signet 9900-1BC Batch Controller System User Manual

Page 10: Batch – batch, Missing – missing signal, Vol puls – volumetric pulse, Time, 0% 100% time

background image

10

9900-1BC Batch Controller Manual

RELA

Y

2

NO

NC

C

RELA

Y

3

NO

NC

C

AC or DC

power

Valve

Flow

ALARM!

AC or DC

power

The alarm is OFF during normal

operation, and will go ON when

relay energizes according to

9900 Relay settings.

Relay Module Wiring

• NO = normally open (closes when energized)
• NC = normally closed (opens when energized)

Relay Mode Settings

*Simple Mode

(See Input Menu - Page 17)

The valve is OFF during normal

operation, and will go ON when

relay energizes according to

9900 Relay settings.

BATCH – Batch*:

Activates relay while batch is running.

0%

100%

Time

MISSING – Missing Signal*:

Activates relay when no fl ow is detected in X seconds
after a batch cycle starts.
(X is user defi ned) Default = 5 seconds.

VOL PULS – Volumetric Pulse*:

Generates a pulse each time a user defi ned volume
is reached.

0%

Flow Input

X

Time

Relay energized

Relay de-energized

% Batch Percentage

Relay energized

Relay de-energized

% Batch Percentage

Relay energized

Relay de-energized