Advanced mode, Relay mode settings - continued, See input menu - page 17) – GF Signet 9900-1BC Batch Controller System User Manual
Page 11
![background image](/manuals/330969/11/background.png)
11
9900-1BC Batch Controller Manual
Advanced Mode
(See Input Menu - Page 17)
EOB PULS – End of Batch Pulse:
Generates a pulse at the end of a batch which can
be used for external counter or to start a second
batch controller.
HI FLOW – High Flow:
In HI FLOW Mode, Relay is energized at Set Flow
value and will be de-energized
at Set Flow value minus Hysteresis value.
If STOP BATCH is set to YES, the hysteresis is
ignored. A batch stopped for a high fl ow condition
will not automatically resume when the fl ow
decreases below the hysteresis level.
User interaction is required to resume the batch.
OVERRUN – Overrun:
Activates relay when Overrun reaches the specifi ed
volume (see Set Overrun Volume, pg. 19).
Note:
The Overrun Alarm Volume must be greater
than the Manual Compensation Volume. If the
Overrun Alarm Volume is less than or equal to the
Manual Compensation Volume, the Overrun Alarm
will activate on every batch.
SRC VOL – Source Volume:
Activates relay when Source Volume falls to specifi ed
volume (
only available when "Source Volume" is ON)
Relay Mode Settings - continued
Relay energized
Relay de-energized
0%
100%
Overrun
Time
Relay energized
Relay de-energized
% Batch Percentage
0%
100%
Time
Relay energized
Relay de-energized
% Batch Percentage
Hysteresis
Time
Process
High
Setpoint
Relay energized
Relay de-energized