EOB PULS – End of Batch Pulse:

Generates a pulse at the end of a batch which can
be used for external counter or to start a second
batch controller.

HI FLOW – High Flow:

In HI FLOW Mode, Relay is energized at Set Flow

value and will be de-energized

at Set Flow value minus Hysteresis value.
If STOP BATCH is set to YES, the hysteresis is
ignored. A batch stopped for a high fl ow condition
will not automatically resume when the fl ow
decreases below the hysteresis level.
User interaction is required to resume the batch.

OVERRUN – Overrun:

Activates relay when Overrun reaches the specifi ed
volume (see Set Overrun Volume, pg. 19).

Note:

The Overrun Alarm Volume must be greater

than the Manual Compensation Volume. If the
Overrun Alarm Volume is less than or equal to the
Manual Compensation Volume, the Overrun Alarm
will activate on every batch.

SRC VOL – Source Volume:

Activates relay when Source Volume falls to specifi ed
volume (

only available when "Source Volume" is ON)

Relay Mode Settings - continued

Relay energized

Relay de-energized

0%

100%

Overrun

Time

Relay energized

Relay de-energized

% Batch Percentage

0%

100%

Time

Relay energized

Relay de-energized

% Batch Percentage

Hysteresis

Time

Process

High

Setpoint

Relay energized

Relay de-energized