Tpi alarms, Printer alarms – Franklin Fueling Systems TS 550 evo Fuel Management System Operators Guide User Manual
Page 39

35
Displayed Alarm /
Warning
Device
Description
Recommended Actions
TPI Alarms
Capacitor Failing
TPI
The STP controller is reporting a
capacitor failure.
Refer to the applicable Smart controller Installation guide for details.
Clogged Intake
TPI
The STP controller has reported
a dry run condition but the
associated tank shows a product
level above the intake.
Ensure proper programming of the TPI and calibration of the Smart
Controller. If correct, check for an obstruction on the PMA.
Communication Failure
TPI
Communication from the TPI to
the STP controller has failed. The
Console is seeing the controller
but the controller is not responding
to commands.
Verify all wiring connections. Call FFS Technical Services Department
for support.
Controller Type Error
TPI
The programmed controller type
does not match what the console
is detecting.
Verify proper programming of the TPI as well as the Smart controller
type and address.
Dry Tank
TPI
The STP Controller has reported
a dry run condition and the
tank level is at or below the
programmed intake.
Ensure proper programming of the TPI and calibration of the Smart
Controller. If correct, add fuel.
Extended Run
TPI
The STP controller is reporting an
extended run condition.
Refer to the applicable Smart Controller Installation guide for details.
Hardware Fault
TPI
The STP controller is reporting
is reporting a hardware fault
condition.
High Temperature
TPI
The STP controller is reporting a
high temperature condition.
Locked Rotor
TPI
The STP controller is reporting a
locked rotor rating.
Not Calibrated
TPI
The STP controller is reporting
that it has not been calibrated.
Open Circuit
TPI
The STP controller is reporting an
open circuit condition.
Over Speed
TPI
The STP controller is reporting an
over speed condition.
Refer to the applicable Smart Controller Installation guide for details
Over Voltage
TPI
The STP controller is reporting an
over voltage condition.
Pump Communication Fail
TPI
Communication from the TPI to
the STP controller has failed.
Check all wiring connections and ensure that there is power supplied
to the Smart Controller.
Pump In Water
TPI
The water level has risen to within
3 inches of the programmed intake
level.
Ensure proper programming of the TPI and calibration of the Smart
Controller. If correct, have water removed from the tank
Relay Fault
TPI
The STP controller is reporting a
relay fault error.
Refer to the applicable Smart Controller Installation guide for details.
Short Circuit
TPI
The STP controller is reporting a
short circuit condition.
Unbalanced Load
TPI
The STP controller is reporting an
unbalanced load condition.
Unbalanced Voltage
TPI
The STP controller is reporting an
unbalanced voltage condition.
Under Voltage
TPI
The STP controller is reporting a
voltage level under 200VAC.
Under Load
TPI
The STP controller is reporting an
underload condition.
Unknown Fault
TPI
The STP controller is reporting an
unknown fault code.
Check fault condition on Smart controller and contact FFS Technical
Services for more information
Printer Alarms
Check Printer
Printer
Printer is out of paper, or the
printer door is open.
Make sure the printer has paper, and the printer door is closed
completely.
Printer Head
Temperature
Printer
Print head high temperature
persists for at least 2 minutes
Printer will resume printing and the alarm will clear after a short cool-
down period. Keep the console area cool and ventilated. If the alarm
does not clear, contact FFS Technical Support.
Printer Motor
Temperature
Printer
Printer motor has exceeded
temperature limit
Allow printer to cool. Keep the console area cool and ventilated. If the
alarm does not clear, contact FFS Technical Support.