beautypg.com

Tpi alarms, Printer alarms – Franklin Fueling Systems TS 550 evo Fuel Management System Operators Guide User Manual

Page 39

background image

35

Displayed Alarm /

Warning

Device

Description

Recommended Actions

TPI Alarms

Capacitor Failing

TPI

The STP controller is reporting a 

capacitor failure.

Refer to the applicable Smart controller Installation guide for details.

Clogged Intake

TPI

The STP controller has reported 

a dry run condition but the 

associated tank shows a product 

level above the intake.

Ensure proper programming of the TPI and calibration of the Smart 

Controller. If correct, check for an obstruction on the PMA.

Communication Failure

TPI

Communication from the TPI to 

the STP controller has failed. The 

Console is seeing the controller 

but the controller is not responding 

to commands.

Verify all wiring connections. Call FFS Technical Services Department 

for support.

Controller Type Error

TPI

The programmed controller type 

does not match what the console 

is detecting.

Verify proper programming of the TPI as well as the Smart controller 

type and address.

Dry Tank

TPI

The STP Controller has reported 

a dry run condition and the 

tank level is at or below the 

programmed intake.

Ensure proper programming of the TPI and calibration of the Smart 

Controller. If correct, add fuel.

Extended Run

TPI

The STP controller is reporting an 

extended run condition.

Refer to the applicable Smart Controller Installation guide for details.

Hardware Fault

TPI

The STP controller is reporting 

is reporting a hardware fault 

condition.

High Temperature

TPI

The STP controller is reporting a 

high temperature condition. 

Locked Rotor

TPI

The STP controller is reporting a 

locked rotor rating.

Not Calibrated

TPI

The STP controller is reporting 

that it has not been calibrated.

Open Circuit

TPI

The STP controller is reporting an 

open circuit condition.

Over Speed

TPI

The STP controller is reporting an 

over speed condition.

Refer to the applicable Smart Controller Installation guide for details

Over Voltage

TPI

The STP controller is reporting an 

over voltage condition.

Pump Communication Fail

TPI

Communication from the TPI to 

the STP controller has failed.

Check all wiring connections and ensure that there is power supplied 

to the Smart Controller.

Pump In Water

TPI

The water level has risen to within 

3 inches of the programmed intake 

level.

Ensure proper programming of the TPI and calibration of the Smart 

Controller. If correct, have water removed from the tank

Relay Fault

TPI

The STP controller is reporting a 

relay fault error.

Refer to the applicable Smart Controller Installation guide for details.

Short Circuit

TPI

The STP controller is reporting a 

short circuit condition.

Unbalanced Load

TPI

The STP controller is reporting an 

unbalanced load condition.

Unbalanced Voltage

TPI

The STP controller is reporting an 

unbalanced voltage condition.

Under Voltage

TPI

The STP controller is reporting a 

voltage level under 200VAC.

Under Load

TPI

The STP controller is reporting an 

underload condition.

Unknown Fault

TPI

The STP controller is reporting an 

unknown fault code.

Check fault condition on Smart controller and contact FFS Technical 

Services for more information    

Printer Alarms

Check Printer

Printer

Printer is out of paper, or the 

printer door is open.

Make sure the printer has paper, and the printer door is closed 

completely.

Printer Head

Temperature

Printer

Print head high temperature 

persists for at least 2 minutes

Printer will resume printing and the alarm will clear after a short cool-

down period. Keep the console area cool and ventilated. If the alarm 

does not clear, contact FFS Technical Support. 

Printer Motor

Temperature

Printer

Printer motor has exceeded 

temperature limit

Allow printer to cool. Keep the console area cool and ventilated. If the 

alarm does not clear, contact FFS Technical Support.