Franklin Fueling Systems TS 550 evo Fuel Management System Operators Guide User Manual
Page 32

28
Displayed Alarm /
Warning
Device
Description
Recommended Actions
Controller Module is
Offline
Slot
Controller Module is offline due to
unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is flashing or steady
try to reboot system. If the condition still exists, contact Franklin
Fueling Systems’ Technical Services Dept. for support on this issue.
DIM module number
mismatch
Slot
DIM modules detected does not
match the number programmed.
Check that the number of DIM Modules installed matches the number
programmed under System Configuration > Modules Expected. If
problem persists, contact FFS Technical Services for support
Internal Error #1
System
There is an internal buffer error
occurring in the gauge.
Contact FFS Technical Services for support
Invalid Configuration
None
The configuration that has been
loaded is not valid.
Verify the file type of the configuration which is being uploaded
Invalid Registration
None
The registration that is loaded is
not valid.
If you have upgraded the site before, use the upgrade tool to restore
the former registration. If you have not upgraded the site before,
contact FFS Technical Services for support.
IO Input Alarm
None
An input on the Input/Output
module has been configured as an
alarm and is active.
Check the programming and voltage inputs for the specified Input
channel on the IO module.
IO Module is offline
Slot
The IO Module is not
communicating with the Console
Inspect the IO module for error lights. If green light is flashing,
recover the module. If the lights are off: Power down, remove / re-
seat the module and power back up. If problem persists, contact FFS
Technical Services for support
IO module number
mismatch
Slot
IO Modules detected does not
match the number programmed.
Check that the number of IO Modules installed matches the num-
ber programmed under System Configuration > Modules Expected.
Check for a flashing green light or no light at all on the IO Module and
contact FFS Technical Services for support.
IS Barrier Violation
None
Non-Intrinsically Safe module
placed in IS area; or IS Barrier is
removed.
Check the module configuration to ensure that a module has not
been improperly placed. Power down and then remove / re-seat the IS
barrier. If problem persists contact FFS Technical Services for support
LON module number
mismatch
Slot
Lon Modules detected does not
match the number of Lon Modules
programmed.
Check that the number of LON Modules installed matches the number
programmed under System Configuration > Modules Expected.
If problem persists, contact FFS Technical Services for support. Also
check that the Node ID does not conflict with another Node ID in the
network
Power Supply Input Alarm
None
An input on the Power Supply has
been configured as an alarm and
is active.
Check the programming and voltage inputs for the specified Low
Voltage Input channel on the Power Supply module.
Power Supply Module
number mismatch
Slot
Power Supply Modules detected
does not match the number
programmed.
Check that the number of Power Supply Modules installed matches
the number programmed under System Configuration > Modules Ex-
pected. Check for a flashing green light or no light at all on the Power
Supply Module and contact FFS Technical Services for support
Power Supply Module is
Offline
Slot
Power Supply Module is offline
due to unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is flashing or steady
try to reboot system. If the condition still exists, contact Franklin
Fueling Systems’ Technical Services Dept. for support on this issue.
Power Supply Module
Setup Error
None
Errors in the setup of the listed
module.
The console may need to be reprogrammed.
Printer Module Number
Mismatch
Slot
Printer Modules detected does not
match the number programmed.
Check that the number of Printer Modules installed matches the
number programmed under System Configuration > Modules
Expected. If problem persists, contact FFS Technical Support.
Probe Module is Offline
Slot
Probe Module is not
communicating with the console.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is flashing or steady,
re-seat module and reboot system. If the condition still exists, contact
Franklin Fueling Systems’ Technical Support for help on this issue.
Probe Module Number
Mismatch
Slot
Probe Modules detected does
not match the number of Probe
Modules programmed.
Check that the number of Probe Modules installed matches the num-
ber programmed under System Configuration > Modules Expected.
Check for a flashing green light or no light at all on the Probe Module
and contact FFS Technical Services for support.
Probe Module Setup Error
None
Programming errors made during
setup of the Probe Module.
Verify Probe Module programming parameters. If the condition still
exists, contact Franklin Fueling Systems’ Technical Support for help
on this issue.
Relay Module is Offline
Slot
Relay Module is offline due to
unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is flashing or steady
try to reboot system. If the condition still exists, contact Franklin
Fueling Systems’ Technical Support for help on this issue.