Displayed Alarm /

Warning

Device

Description

Recommended Actions

Controller Module is

Offline

Slot

Controller Module is offline due to 

unknown causes.

Follow safety procedures before working inside the console. Visually 

verify a steady green “Run” light. If red “Err” light is flashing or steady 

try to reboot system. If the condition still exists, contact Franklin 

Fueling Systems’ Technical Services Dept. for support on this issue.

DIM module number

mismatch

Slot

DIM modules detected does not 

match the number  programmed.

Check that the number of DIM Modules installed matches the number 

programmed under System Configuration > Modules Expected. If 

problem persists, contact FFS Technical Services for support

Internal Error #1

System

There is an internal buffer error 

occurring in the gauge.

Contact FFS Technical Services for support

Invalid Configuration

None

The configuration that has been 

loaded is not valid.

Verify the file type of the configuration which is being uploaded

Invalid Registration

None

The registration that is loaded is 

not valid.

If you have upgraded the site before, use the upgrade tool to restore 

the former registration. If you have not upgraded the site before, 

contact FFS Technical Services for support.

IO Input Alarm

None

An input on the Input/Output 

module has been configured as an 

alarm and is active.

Check the programming and voltage inputs for the specified Input 

channel on the IO module.

IO Module is offline

Slot

The IO Module is not 

communicating with the Console

Inspect the IO module for error lights. If green light is flashing, 

recover the module. If the lights are off: Power down, remove / re-

seat the module and power back up. If problem persists, contact FFS 

Technical Services for support

IO module number

mismatch

Slot

IO Modules detected does not 

match the number programmed.             

Check that the number of IO Modules installed matches the num-

ber programmed under System Configuration > Modules Expected. 

Check for a flashing green light or no light at all on the IO Module and 

contact FFS Technical Services for support.

IS Barrier Violation

None

Non-Intrinsically Safe module 

placed in IS area; or IS Barrier is 

removed.

Check the module configuration to ensure that a module has not 

been improperly placed. Power down and then remove / re-seat the IS 

barrier. If problem persists contact FFS Technical Services for support

LON module number

mismatch

Slot

Lon Modules detected does not 

match the number of Lon Modules 

programmed.       

Check that the number of LON Modules installed matches the number 

programmed under System Configuration > Modules Expected. 

If problem persists, contact FFS Technical Services for support. Also 

check that the Node ID does not conflict with another Node ID in the 

network

Power Supply Input Alarm

None

An input on the Power Supply has 

been configured as an alarm and 

is active.

Check the programming and voltage inputs for the specified Low 

Voltage Input channel on the Power Supply module.

Power Supply Module

number mismatch

Slot

Power Supply Modules detected 

does not match the number 

programmed. 

Check that the number of Power Supply Modules installed matches 

the number programmed under System Configuration > Modules Ex-

pected. Check for a flashing green light or no light at all on the Power 

Supply Module and contact FFS Technical Services for support

Power Supply Module is

Offline

Slot

Power Supply Module is offline 

due to unknown causes.

Follow safety procedures before working inside the console. Visually 

verify a steady green “Run” light. If red “Err” light is flashing or steady 

try to reboot system. If the condition still exists, contact Franklin 

Fueling Systems’ Technical Services Dept. for support on this issue.

Power Supply Module

Setup Error

None

Errors in the setup of the listed 

module.

The console may need to be reprogrammed.

Printer Module Number

Mismatch

Slot

Printer Modules detected does not 

match the number programmed.

Check that the number of Printer Modules installed matches the 

number programmed under System Configuration > Modules 

Expected. If problem persists, contact FFS Technical Support.

Probe Module is Offline

Slot

Probe Module is not 

communicating with the console.

Follow safety procedures before working inside the console. Visually 

verify a steady green “Run” light. If red “Err” light is flashing or steady, 

re-seat module and reboot system. If the condition still exists, contact 

Franklin Fueling Systems’ Technical Support for help on this issue.

Probe Module Number

Mismatch

Slot

Probe Modules detected does 

not match the number of Probe 

Modules programmed.

Check that the number of Probe Modules installed matches the num-

ber programmed under System Configuration > Modules Expected. 

Check for a flashing green light or no light at all on the Probe Module 

and contact FFS Technical Services for support.

Probe Module Setup Error

None

Programming errors made during 

setup of the Probe Module.

Verify Probe Module programming parameters. If the condition still 

exists, contact Franklin Fueling Systems’ Technical Support for help 

on this issue.

Relay Module is Offline

Slot

Relay Module is offline due to 

unknown causes. 

Follow safety procedures before working inside the console. Visually 

verify a steady green “Run” light. If red “Err” light is flashing or steady 

try to reboot system. If the condition still exists, contact Franklin 

Fueling Systems’ Technical Support for help on this issue.