beautypg.com

Scm alarms – Franklin Fueling Systems TS 550 evo Fuel Management System Operators Guide User Manual

Page 36

background image

32

Displayed Alarm /

Warning

Device

Description

Recommended Actions

SCM Alarms

Containment Not

Learned

SCM

The learning process has not been 

completed.

Refer to Secondary Containment Monitoring Installation and User’s 

Guide 000-0528 for more information.

Containment Program

Error Detected

SCM

An error has been detected in the 

containment programming.

Containment Program

Error Warning

SCM

An error has been detected in the 

containment programming

Containment Pump

Request Ignored

Engineering The containment called for the 

STP to turn on but has not seen an 

increase in vacuum level.

Failed to Hold Vacuum

SCM

The rate of vacuum decay faster 

than the learned rate.

Failed to Reach Target

Vacuum

SCM

6”hg could not be reached in the 

learned time.

Low Vacuum

SCM

The vacuum level has dropped 

below 1”hg.

Low Vacuum And Pump

Request Ignored

Engineering Low vacuum level due to Pump 

Request Ignored.

Not Configured

SCM

Containment programming has not 

been completed

Unstable Vacuum

SCM

Vacuum level is fluctuating at a rate 

that is FFSsistent with the learned 

parameters.

Vacuum Sensor Failed

SCM

The 4-20mA vacuum transducer 

has failed and is no longer 

detected

Vacuum Too High

SCM

The vacuum level has reached 

above 10”hg