Line Leak Detector (LLD) Alarms

0.1 GPH Compliance

Expired

Line

A 0.1 gph test has not been 

completed within the last 365 

days.

Verify that no pertinent alarm conditions have been reoccurring. 

Ensure that there is enough time to pass the test.

0.2 GPH Compliance

Expired

Line

A 0.2 gph test has not been 

completed within the last 30 days.

Verify that no pertinent alarm conditions have been reoccurring. 

Ensure proper seating pressure. If Firmware revision is older 

than 1.7.4.5535, upgrade to make use of the Statistical Line Leak 

Detection enhancement.

3 GPH Compliance

Expired

Line

The required daily 3 GPH test has 

not been completed.

Check for continuous pump on conditions that could be caused by a 

sticky handle switch or relay.

Air in Line

Line

Air has been detected in the line.

Purge all air from the line starting at the furthest dispenser and 

working in toward the STP. Verify tightness of lines and investigate 

other sources for air infiltration.

Dispensing Pressure Test

Failed

Line

Pressure during dispensing 

dropped below 7.5 psi. This is 

seen as a catastrophic leak during 

dispensing.

Inspect all sumps for product. Use a pressure gauge to test line 

pressure during dispensing. See “LS500 Auto Learn Line Leak 

Detection Installation & User’s Guide” FFS 000-2145. Contact 

Franklin Fueling Systems’ Technical Services Dept. for support.

Extended Hook Signal

Line

A hook signal has been detected 

for more than 60 minutes with the 

line pressure staying the same.

Check for voltage to the AC-Input module. If issue still exists contact 

Franklin Fueling Systems’ Technical Services Dept. for support.

Failed to Catch Pressure

Line

The pump OFF pressure has 

dropped below 7 psi within 

1 second after the pump was 

turned off

Inspect all sumps for product. Refer to “LS500 Auto Learn Line 

Leak Detection Installation & User’s Guide” FFS 000-2145 for more 

information.

Failed to Pressure Up

Line

The Line has called for the pump 

to turn on but did not see the 

pressure increase

Inspect all sumps for product. Refer to “LS500 Auto Learn Line 

Leak Detection Installation & User’s Guide” FFS 000-2145 for more 

information.

Gross Leak Detected

Line

The console has detected a line 

leak greater than 3 gph.

Inspect all sumps for product. Refer to “LS500 Auto Learn Line 

Leak Detection Installation & User’s Guide” FFS 000-2145 for more 

information.

High Pump Pressure

Line

The Pump Off pressure has 

stayed above 49 psi for 3 

consecutive times.

Inspect all sumps for product. Ensure that no other check valves are 

used within the system. Observe multi-point line pressure readings 

during pump on and off using a pressure gauge in the line. If line 

pressure is high, there may be a blockage in the line. Refer to “LS500 

Auto Learn Line Leak Detection Installation & User’s Guide” 

FFS 000-2145 for more information.

Line is not configured

Line

Specified line is not configured, 

therefore line leak test will not be 

performed.

Verify line programming. If necessary configure line.

Line Not Learned

Line

Specified line not learned.

Complete learn process, if any learn alarms occur follow the 

proper procedure. Refer to “LS500 Auto Learn Line Leak Detection 

Installation & User’s Guide” FFS 000-2145 for more information.

Line Program Error

Detected

Line

An error has been detected in the 

programming of the specified line.

Verify programming of line under the setup menu.

Line Pump Request

Ignored

Engineering The line has called for the pump 

to be turned on but another 

application is currently using the 

STP   

Verify that other applications are operating properly. Contact Franklin 

Fueling Systems’ Technical Services Dept. for support.

Marginal Pass of Gross

Leak Test

Line

The last passed gross test 

detected a leak just under the 

3 gph threshold.

Verify there is no sign of leaks within any of the sumps. Run 

additional tests. Refer to “LS500 Auto Learn Line Leak Detection 

Installation & User’s Guide” FFS 000-2145 for more information.

Monthly Leak Test Failed

Line

The Console has detected a line 

leak greater than 0.2 gph.

Inspect all sumps for product. Refer to “LS500 Auto Learn Line 

Leak Detection Installation & User’s Guide” FFS 000-2145 for more 

information.

Not Enabled

Line

Line testing has not been enabled. Verify no other alarm is present then enter the line control menu and 

enable the line testing feature.    

Precision Leak Test Failed

Line

0.1 GPH Line leak test failed.

Follow site policy on line leak procedures.

Pressure Transducer Fail

Line

The transducer is not being 

detected by the console.

Inspect the wiring to the specified transducer and the channel it 

terminates at. Refer to “LS500 Auto Learn Line Leak Detection 

Installation & User’s Guide” FFS 000-2145 for more information.

Sudden Pressure Loss

Line

During a 45 minute quite period 

the pressure was seen to drop by 

a 2 times the learned 3 gph slope.

Inspect all sumps for product. Refer to “LS500 Auto Learn Line 

Leak Detection Installation & User’s Guide” FFS 000-2145 for more 

information.