Franklin Fueling Systems TS 550 evo Fuel Management System Operators Guide User Manual
Page 22

18
Reasons Why SCALD May Not Complete
• No Quiet Time
• SCALD needs four 20 minute QIs in order to
complete a test. These QIs are normally found in the
early morning hours. If the site is so busy that there
are no 20 minute periods of no dispensing, then
SCALD will not be able to complete a test.
• Temperature Instability
• If a site is receiving deliveries frequently and the
temperature of the fuel being delivered is several
degrees hotter/colder then the fuel in the tank,
SCALD will not be able to collect data due to thermal
instability interrupting quiet time. The temperature of
the fuel cannot change more than .01° F during a 20
minute QI.
• If a pump control relay is stuck closed and the pump
is running all of the time, the temperature in the tank
may be much higher than in the other tanks. Due to
this high temperature and the fact that the pump is
running, no QIs will be collected.
Note: On rare occasions conditions can arise that prevent
SCALD from getting enough QIs to complete a test.
Viewing SCALD results
From the Quick Jump menu, select Compliance and then
select Tanks.
Tank Leak Test Reports
Reports that contain leak testing data and results may be
printed from the console or generated/printed using TSA.
Printing Tank Leak Test Reports
LCD
1. Starting at the Home screen, open the QJM and select
Reports.
2. From the Report Type menu select either the Tank Test
(for static reports) or SCALD for continuous reports.
3. Select the Date Range desired.
4. Press the checkmark to start report printi