GE Industrial Solutions 6KCV300WPD User Manual
Page 162
![background image](/manuals/295733/162/background.png)
GEL100340
tmr
Retriggerable monostable timer.
Timer is activated on every rising edge of input g in the following way:
1. On the rising edge of input g the following operations are performed:
l
Reading activation time from input t.
l
Zero setting of internal variable act (output act).
l
Set output o TRUE.
.
After t cycles are elapsed, from operations start, timer outputs are set in the following
way:
l
output o is set FALSE
l
output act stops on the last value reached
value)
2 . if, while the timer is active, input g became FALSE, timer goes on work normaly
3 . if, while the timer is active a new rising edge on input g is checked, timer executes a new cycle
repeating the operations starting from point 1.
When the timer is active, output o is TRUE, output act indicates the number of milliseconds elapsed from
operations start. When output o is FALSE output act is not significant.
Input
is read only in the cycle in which the rising cycle of input g is checked. Therefore, if
changes
while timer is enabled, output o is TRUE, the new value is not considered. This value will be used in the next
activation timer.
All times are expressed in milliseconds. Therefore, if input
is set 8, output o becomes TRUE for 8
milliseconds and output act changes from 0 to 8.
Input ports
name
alternative type function
int
operations
start and timer enable
t
int
number of cycles of timer activation
1 5 2