– 84 –

Block distinction

Check

code

Block

Outdoor P.C.
board

Not
displayed

Outdoor P.C.
board

Others
(including
compres-
sor)

Operation of diagnosis function

Check

code

Cause of operation

Current-detect circuit
error

Being out of place,
disconnection or short-
circuit of outdoor temp.
sensor (Ts)

Disconnection or short-
circuit of discharge
temp. sensor

Outdoor fan drive
system error

Outdoor temp. sensor
error

Compressor drive
output error, Compres-
sor error (lock, missing,
etc.), Break down

Error exclusive for
multiple type

Return serial signal has
been sent when
operation started, but it
is not sent from
halfway.
(1) Compressor thermo.

operation
Gas shortage
Gas leak

(2) Instantaneous

power failure

Compressor does not
rotate.
(Current protective
circuit does not operate
when a specified time
passed after compres-
sor had been acti-
vated.)

Discharge temp.
exceeded 117°C

Break down of
compressor

Remarks

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

——

Displayed when
error is detected.

Displayed when
error is detacted.

Flashes when
trouble is detected
on return serial
signal, and normal
status when signal
is reset.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

Air

conditioner

status

All off

All off

All off

All off

Operation
continues

All off

All off

Operation
continues

All off

All off

All off

Judgment and action

Even if trying operation again, all
operations stop immediately. :
Replace P.C. board.

Check 5-serial LED.
1. Check outdoor temp. sensors

(TE, TS).

2. Check P.C. board.

1. Check discharge temp. sensor

(TD).

2. Check P.C. board

Position-detect error, over-current
protective operation of outdoor fan
drive system, fan lock, etc. :
Replace P.C. board or fan motor.

1. Check outdoor temp. sensor

(TO).

2. Check P.C. board.

Check 5-serial LED.
When 20 seconds passed after
start-up, position-detect circuit
error occurred. : Replace
compressor.

Check 5-serial LED.
1. Miswiring of connecting wire of

A/B rooms in indoor/outdoor
units

2. Check gas leakage.
3. Check disconnection of sensor.
4. Electronic control valve error

1. Repeat Start and Stop with

interval of approx. 10 to 40
minutes. (Code is not displayed
during operation.)
Supply gas. (Check also gas
leak).

2. Unit operates normally during

check.
If return serial signal does not
stop between indoor terminal
block 2 and 3, replace inverter
P.C. board.
If signal stops between indoor
terminal block 2 and 3, replace
indoor P.C. board.

1. Trouble on compressor
2. Trouble on wiring of compres-

sor (Missed phase)

1. Check dischage temp. sensor

(TD).

2. Gas leakage
3. Trouble on P.M.V.

1. Check power voltage.

(220–230–240 V +10%)

2. Overload operation of refrigera-

tion cycle
Check installation condition
(Short-circuit of outdoor diffuser).